Appendix C. FOUNDATION fieldbus Block Information
C.4 DISPLAY TRANSDUCER BLOCK
The Display Transducer block (TB 1300) includes parameters for setup of the
2230 Graphical Field Display for use in a FOUNDATION Fieldbus system.
Table C-6. Display Transducer
Block
Index
Number Parameter Description
1 ST_REV The revision level of the static data associated with the
function block. The revision value increments each time a
static parameter value in the block is changed.
2 TAG_DESC The user description of the intended application of the
block.
3 STRATEGY The strategy field can be used to identify grouping of
blocks. This data is not checked or processed by the block.
4 ALERT_KEY The identification number of the plant unit. This information
may be used in the host for sorting alarms, etc.
5 MODE_BLK The actual, target, permitted, and normal modes of the
block.
Target: The mode to “go to”
Actual: The mode the “block is currently in”
Permitted: Allowed modes that target may take on
Normal: Most common mode for target
6 BLOCK_ERR This parameter reflects the error status associated with the
hardware or software components associated with a block.
It is a bit string, so that multiple errors may be shown.
7 UPDATE_EVT This alert is generated by any change to the static data.
8 BLOCK_ALM The 2230 transducer block does not support update of
BLOCK_ALM information, and it does not publish
BLOCK_ALM on segment/FF bus.
9 TRANSDUCER_DIRECTORY Directory that specifies the number and starting indices of
the transducers in the transducer block.
10 TRANSDUCER_TYPE Identifies the transducer.
11 TRANSDUCER_TYPE_VER
12 XD_ERROR A transducer block alarm subcode. Provides additional
error codes related to transducer blocks.
13 COLLECTION_DIRECTORY A directory that specifies the number, starting indices, and
DD Item ID’s of the data collections in each transducer
within a transducer block.
14 MAO_1_INPUT_1 TANK_NUMBER
TANK_PARAMETER
ENGINEERING_UNIT
MIN_VALUE
MAX_VALUE
15 MAO_1_INPUT_2
16 MAO_1_INPUT_3
17 MAO_1_INPUT_4
18 MAO_1_INPUT_5
19 MAO_1_INPUT_6
20 MAO_1_INPUT_7
21 MAO_1_INPUT_8
22 MAO_2_INPUT_1
23 MAO_2_INPUT_2
24 MAO_2_INPUT_3