Section 3. Installation
3.3.8 2230 in
F
OUNDATION
fieldbus systems
The Rosemount 2230 Display supports the FOUNDATION fieldbus (FF)
technology and lets you integrate a 2230 into an existing FF network. As long
as the power supply meets certain requirements (see Figure 3-5 and
Figure 3-6) the 2230
(1)
will be able to operate as any other FF device.
Figure 3-5. Example of an I.S.
FOUNDATION fieldbus system
Ensure that the power supply is able to provide the total current needed for all
the connected devices. See “Power Requirements” on page 3-7 for further
information.
Ensure that the 2230 and other devices connected to the FOUNDATION
fieldbus (FF) system are compliant with the FISCO or Entity parameters of the
power supply.
Ensure that the short circuit protection of the Segment Coupler
(2)
matches the
current consumption of the connected devices.
Figure 3-6. Example of a
Non-I.S. FOUNDATION fieldbus
system
(1) See Appendix B: Product Certifications for 2230 approval information
5900S Radar Level
Gauge
2240S Temperature
Transmitter
2230 Display
FISCO/Entity compliant
FM USA, FM Canada:
AIS Class I, Division 1
ATEX and IECEx:
Ex [ia], or Ex [ib] (FISCO)
Ex [ia] (Entity)
Segment
Coupler
I.S. Power Supply
Trunk
(2) See the Rosemount 2410 Reference Manual (Document No. 300530EN) for more informa-
tion on the Segment Coupler.
5900S Radar Level
Gauge
2230 Display
Barrier
IS Trunk
SAFE AREA HAZARDOUS AREA
Segment
Coupler
Non-I.S. Power Supply
FISCO/Entity compliant
FM USA, FM Canada:
AIS Class I, Division 1
ATEX and IECEx:
Ex [ia], or Ex [ib] (FISCO)
Ex [ia] (Entity)
2240S Temperature
Transmitter