Emerson 2230 Marine Sanitation System User Manual


 
Reference Manual
00809-0100-2230, Rev BB
August 2014
Rosemount 2230
4-28
Section 4. Configuration and Operation
The following table displays all possible configurations of the WRITE_LOCK
parameter.
Table 4-6. Possible configuration of the WRITE_LOCK parameter.
4.12.2 MAX_NOTIFY The MAX_NOTIFY parameter value is the maximum number of alert reports
that the resource can have sent without getting a confirmation, corresponding
to the amount of buffer space available for alert messages. The number can
be set lower, to control alert flooding, by adjusting the LIM_NOTIFY
parameter value. If LIM_NOTIFY is set to zero, then no alerts are reported.
FEATURE_SEL
HARDW_LOCK bit
FEATURE_SEL
SOFTW_LOCK bit
SECURITY
SWITCH WRITE_LOCK
WRITE_LOCK
Read/Write
Write access to
blocks
0 (off) 0 (off) NA 1 (unlocked) Read only All
0 (off) 1 (on) NA 1 (unlocked) Read/Write All
0 (off) 1 (on) NA 2 (locked) Read/Write Function Blocks
Only
0 (off) 1 (on) NA 2 (locked) Read/Write None
1 (on) 0 (off)
(1)
0 (unlocked) 1 (unlocked) Read only All
1 (on) 0 (off) 1 (locked) 2 (locked) Read only Function Blocks
Only
1 (on) 0 (off) 1 (locked) 2 (locked) Read only None
(1) The hardware and software write lock select bits are mutually exclusive and the hardware select has the highest priority. When the
HARDW_LOCK bit if set to 1 (on), the SOFTW_LOCK bit is automatically set to 0 (off) and is read only.