Emerson 2230 Marine Sanitation System User Manual


 
Reference Manual
00809-0100-2230, Rev BB
August 2014
5-9
Rosemount 2230
Section 5. Service and Troubleshooting
5.3.3 Foundation Fieldbus System
This section covers Rosemount Tank Gauging systems in FOUNDATION
fieldbus networks.
Table 5-5. Troubleshooting
chart for Foundation Fieldbus
related problems
Configuration of communication
protocol
In TankMaster WinSetup:
open the Protocols folder and check that the protocol
channel is enabled
check the protocol channel configuration (right-click the
protocol channel MbMaster icon, choose the Properties
option, and check port, parameters, modem)
Field Bus Modem (FBM)
Check that the FBM is connected to the right port on the
control room PC
Check that the FBM is connected to the right port on the
2160 Field Communication Unit (FCU)
Connection to 2160 FCU
Check that the right field bus port on the 2160 FCU is
connected to the Primary bus on the 2410 Tank Hub
Check communication port LED:s inside the Field
Communication Unit 2160 (FCU)
Activity indicator shows a warning
symbol
Communication failure Check that the 2230 is configured in the 2410 tank database.
See the Raptor System Configuration Manual (Document no.
300510EN) for more information on how to configure the 2410
tank database.
Symptom (continued) Possible cause Action
Symptom Possible cause Action
No communication with the
Rosemount 2230
No temporary address available in the
FOUNDATION fieldbus segment
There is more than four new devices on the FOUNDATION
fieldbus segment. Wait until a temporary address is available.
The device address is within a range
that is not probed by the Link Active
Scheduler (LAS)
Make sure that the device address is scanned by the LAS.
Missing or too many terminations Ensure that there are two terminations on the FOUNDATION
fieldbus segment.
Configuration can not be saved
Write protection switch is set to the
ON position
Software Write Protect is enabled
Check write protection switch on the 2230
Disable software write protect. See “Write Protection” on
page 5-25.
Activity indicator shows a warning
symbol
Communication failure
Out of Service (OOS)
See “No communication with the Rosemount 2230”
Set the device to “Auto” mode
Wrong unit appears on the
display
Incorrect configuration in AMS
Device Manager. Measurement
unit that was chosen in the Display
Setup window does not match
selected unit in the Manual Setup
window
Ensure that the “Default” option is selected for Unit in the
Manual Setup window
Cannot commission the 2230 to
Foundation fieldbus segment
Missing Device Description (DD)
Add Rosemount 2230 DD to the FF host