Emerson 2230 Marine Sanitation System User Manual


 
Reference Manual
00809-0100-2230, Rev BB
August 2014
Rosemount 2230
2-10
Section 2. Overview
2.3.1 System Start-up The standard start-up procedure of a Rosemount Tank Gauging system that
includes devices such as the 2160 Field Communication Unit, 2410 Tank
Hub, 5900S Radar Level Gauge, and the 2240S Multi-input Temperature
Transmitter can be summarized as follows:
1. Install the devices on the appropriate locations.
2. Assign Modbus addresses
(1)
for the Rosemount 2410 Tank Hub, for level
gauges such as the 5900S Radar Level Gauge, and for auxiliary tank
devices (ATD) such as the 2240S Multi-input Temperature Transmitter.
The Modbus addresses will be stored in the built-in databases of the
Rosemount 2410 Tank Hub and the Rosemount 2160 Field
Communication Unit.
3. Verify that the total current consumption of devices connected to the
Tankbus does not exceed 250 mA
(2)
. In a Smart Wireless System the
maximum current is 200 mA.
4. Wire the devices.
Connect field devices to the Tankbus.
Note! Devices must be configured in the tank database
(1)(2)
of the
Rosemount 2410 Tank Hub in order to be able to communicate on the
Tankbus.
Connect the Rosemount 2410 Tank Hub to the Rosemount 2160 Field
Communication Unit.
Connect the Rosemount 2160 Field Communication Unit to the control
room PC with TankMaster software. The 2160 may be connected via a
Rosemount 2180 Field Bus Modem, or directly via RS 232 or RS 485.
5. Install the TankMaster software in the control room PC.
6. Configure the devices by using the TankMaster WinSetup configuration
tool as described in the Rosemount Raptor System Configuration
Manual (Document no. 300510EN).
FOUNDATION Fieldbus
To start up Rosemount Tank Gauging devices in a FOUNDATION fieldbus
system:
1. Prepare the start-up by recording information that will be needed for
configuration of various field devices as described in the Rosemount
Raptor System Configuration manual. This may for example include tank
geometry, antenna type, number of temperature elements and other
configuration parameters.
2. Connect the field devices, such as the Rosemount 5900S Radar Level
Gauge and the Rosemount 2240S Multi-input Temperature Transmitter,
to the FOUNDATION fieldbus network.
3. Configure the field devices by using the AMS Device Manager.
See the Reference Manual for the respective field device and the Rosemount
Raptor System Configuration manual (Document No. 300510) for more
information on how to configure various Raptor devices. See section
“Technical Documentation” on page 1-4 for a list of available documentation.
(1) See the Rosemount Raptor System Configuration Manual (Document no. 300510) for more
information
(2) See the Rosemount 2410 Tank Hub Reference Manual, Document No. 300530 for more
information