Emerson 2230 Marine Sanitation System User Manual


 
Reference Manual
00809-0100-2230, Rev BB
August 2014
4-25
Rosemount 2230
Section 4. Configuration and Operation
4.10.2 Factory
Configuration
The following fixed configuration of function blocks is provided:
Table 4-5. Available function
blocks for the 2230
4.11 MULTIPLE ANALOG
OUTPUT BLOCKS
To show input data from MAO blocks on the display, the 2230 needs to be
configured by using FOUNDATION fieldbus parameters available in the Display
Transducer Block (see “Display Transducer Block” on page C-10).
4.11.1 Configure the
MAO Blocks
The MAO Block is used for receiving measurement data from devices such as
the Rosemount 5900S Radar Level Gauge. The Rosemount 2230 is supplied
with four pre-configured MAO blocks according to Table 4-5 on page 4-25.
Each MAO block has eight inputs.
Note that the CHANNEL parameter value has to be equal to 1 (auto) in order
to provide data output from the MAO block.
An example of a setup with a Rosemount 2230 receiving data from a
Rosemount 5900S and a Rosemount 2240S is shown in Figure 4-35 on
page 4-26.
Function Block Index Default Tag Available
Multiple Analog Output 1400 MAO_1400 Permanent
Multiple Analog Output 1500 MAO_1500 Permanent
Multiple Analog Output 1600 MAO_1600 Permanent
Multiple Analog Output 1700 MAO_1700 Permanent