Emerson 2230 Marine Sanitation System User Manual


 
Reference Manual
00809-0100-2230, Rev BB
August 2014
Rosemount 2230
www.rosemount-tg.com
Section 2 Overview
2.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 2-1
2.2 2230 Components . . . . . . . . . . . . . . . . . . . . . . . . . . .page 2-2
2.3 System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . .page 2-3
2.4 Installation procedure . . . . . . . . . . . . . . . . . . . . . . .page 2-11
2.1 INTRODUCTION The Rosemount 2230 Graphical Field Display presents inventory tank
gauging data such as level, temperature, and pressure. The 2230 Display
communicates with the Rosemount 2410 Tank Hub via the intrinsically safe
2-wire Tankbus
(1)
. The 2230 also supports installation in Foundation fieldbus
systems.
A 2230 connected to the multiple tank version of the 2410 Tank Hub allows
you to view data from several tanks. It is possible to configure presentation of
measurement variables for each tank individually.
The four softkeys at the front of the 2230 allow you to navigate through the
different menus and provides all tank data, directly on the field.
Data from a group of tanks is buffered by a 2160 Field Communication Unit
(FCU), and is distributed via the Group Bus to a TankMaster PC, or a host
system, whenever the FCU receives a request for data. In case no FCU is
included in the system, the 2410 Tank Hub can communicate directly with the
host computer.
Figure 2-1. System integration
(1) The intrinsically safe Tankbus complies with the FISCO FOUNDATION™ fieldbus standard.
See reference document IEC/TS 60079-27.
TankMaster
2410 Tank Hub
Modem
2160 Field
Communication Unit
Relay outputs
Secondary bus
Primary Bus
Tankbus
2240S Temperature
Transmitter
2230 Display
Group Bus
5900S Radar
Level Gauge