19
Setting the motor
2.3 Setting the motor
This inverter is factory-set to run the dedicated motor (SF-V5R (1500r/min series) with PLG)
(It is not necessary to reset the inverter if you use the dedicated motor (SF-V5R (1500r/min series) with PLG) (only
when inverter capacity = motor capacity).)
2.3.1 Dedicated motor (SF-V5R (1500r/min series))
1Check that the Pr.71 "applied motor" (extended mode) setting is "30" (SF-V5R) (factory setting value).
2.3.2 Motor one rank lower than the dedicated motor (SF-V5R (1500r/min series))
(1) Set the parameter shown below.
POINT
The parameter below is extended mode parameter. Set "1" in Pr. 160 "extended function selection".
Parameter Name Factory Setting Setting Range
80 Motor capacity Inverter capacity 0.4kW to 55kW