Mitsubishi Electronics FR-V500 Marine Battery User Manual


 
69
PARAMETERS
Function list (Extended function
parameters)
Protective functions
870 Speed deviation level
If the difference between speed command value and speed exceeds the setting of the
speed deviation level (Pr. 870) for longer than the setting of the speed deviation time
(Pr. 871), speed deviation excessive "E.OSD" is displayed and the motor stops.
0 to 1500r/min, 9999
0 to 100s
9999
"
""
"
××
871 Speed deviation time
12s
"
""
"
××
873 Speed restriction
0 to 3600r/min 600r/min
×
"
""
"
×
874 OLT level setting
Set the load level of the motor at which OLT alarm.
0 to 200%
150%
"
""
"
×
"
""
"
Operation selection
functions
875 Fault definition
You can classify faults into a minor fault and major faults according to the alarms, and
make setting to select between immediate output shutoff and output shutoff after
deceleration to stop.
0: Immediate output shutoff
1: Output shutoff after deceleration to stop (Immediate output shutoff other than OHT
and THM)
0
"
""
""
""
"
×
876
Thermal relay
protector input
When using the motor provided with PLG, you can input the contact signal of a thermal
relay etc. to terminal OH to provide motor protection against overheat.
0: None
1: Thermal relay input available
1
"
""
""
""
""
""
"
Control system functions
877
Speed feed forward
control/model
adaptive speed
control selection
Select speed feed forward control (which improves the motor trackability in response to
a speed command change (during acceleration/deceleration)) or model adaptive speed
control (that can adjust speed trackability and motor disturbance torque response level
individually). (0: No selection, 1: Speed feed forward control, 2: model adaptive speed
control)
0
"
""
"
×
"
""
"
878
Speed feed forward
filter
Set the primary delay filter for the speed feed forward result calculated using the speed
command and load inertia ratio.
0 to 1s
0s
"
""
"
×
"
""
"
879
Speed feed forward
torque restriction
Restricts the maximum value of the speed feed forward torque.
0 to 400%
150%
"
""
"
×
"
""
"
880 Load inertia ratio
Set the load inertia ratio. Inertia ratio found by easy gain turning. 0, 1 to 200 times 7
"
""
"
×
"
""
"
881
Speed feed forward
gain
Set the feed forward calculation result as a gain.
0 to 100%
0%
"
""
"
×
"
""
"
Maintenance
functions
890
Maintenance output
setting time
Signal outputs and functions for indicating that the cumulative energization time of the
inverter has reached a given time. (Used for warning that the capacitor life is reached,
for example.)
Pr.890:0 to 9998, 9999: No setting
Pr.891:0 to 9998
Pr.892:0
9999
"
""
""
""
""
""
"
891
Maintenance output
timer
0
"
""
""
""
""
""
"
892
Maintenance output
signal clear
0
"
""
""
""
""
""
"
Calibration functions
900
DA1 terminal
calibration
For calibration of external meter
"
""
""
""
""
""
"
901
DA2 terminal
calibration
For calibration of external meter
"
""
""
""
""
""
"
902
Speed setting No.2
bias
You can set the magnitude of the output in response to the speed setting signal (0-
10VDC) as desired.
0 to 10V, 0 to 3600r/min
0V, 0r/
min
"
""
""
""
""
""
"
903
Speed setting No.2
gain
You can set the magnitude of the output in response to the speed setting signal (0-
10VDC) as desired.
0 to 10V, 0 to 3600r/min
10V,
1500r/min
"
""
""
""
""
""
"
904
Torque command
No.3 bias
You can set the magnitude of the output in response to the torque setting signal
(0±10VDC) as desired.
0 to 10V, 0 to 400%
0V, 0%
"
""
""
""
""
""
"
905
Torque command
No.3 gain
You can set the magnitude of the output in response to the torque setting signal
(0±10VDC) as desired.
0 to 10V, 0 to 400%
10V,
150%
"
""
""
""
""
""
"
917
No. 1 terminal bias
(Speed)
You can set the magnitude of the output in response to the No. 1 terminal analog
setting signal (0±10VDC) as desired.
0 to 10V, 0 to 3600r/min
0V,
0r/min
"
""
""
""
""
""
"
918
No. 1 terminal gain
(Speed)
You can set the magnitude of the output in response to the No. 1 terminal analog
setting signal (0±10VDC) as desired.
0 to 10V, 0 to 3600r/min
10V,
1500r/min
"
""
""
""
""
""
"
919
No. 1 terminal bias
(torque/magnetic flux)
You can set the magnitude of output (torque/magnetic flux) in responce to the No.1
terminal analog set signal (DC0 ±10V) as desired.
0 to 10V, 0 to 400%
0V, 0%
"
""
""
""
""
""
"
920
No. 1 terminal gain
(torque/magnetic flux)
You can set the magnitude of output (torque/magnetic flux) in responce to the No.1
terminal analog set signal (DC0 ±10V) as desired.
0 to 10V, 0 to 400%
10V,
150%
"
""
""
""
""
""
"
Additional
functions
990 Buzzer control
You can control the "beep" sound produced when any key of the parameter unit is
pressed.
0: Without sound
1: With sound
1
"
""
""
""
""
""
"
991
Parameter for the option (FR-PU04V)
Function
Parameter
Name Outline
Factory
Setting
Cus-
tomer
Set-
ting
At-a-glance Guide to Func-
tions
"
""
": Usable function
×: Unusable function
* :
Functions that can be used
for parameter-set position con-
trol
Vector Control
Speed
control
Torque
control
Position
control
CAUTION
Use this function when a difference in speed will constitute a hindrance. It is
independent of torque control.