Mitsubishi Electronics FR-V500 Marine Battery User Manual


 
58
PARAMETERS
Parameter
5
Function list (Extended function
parameters)
Operation selection functions
75
Reset selection/
disconnected PU
detection/PU stop
selection
You can select the reset input acceptance, disconnected PU detection function and PU
stop function.
14
"
""
""
""
""
""
"
77
Parameter write
disable selection
0,1,2 0
"
""
""
""
""
""
"
78
Reverse rotation
prevention selection
You can prevent any reverse rotation fault resulting from the mis-input of the start
signal.
0: Both forward rotation and reverse rotation enabled, 1: Reverse rotation disabled, 2:
Forward rotation disabled
0
"
""
""
""
""
""
"
79
Operation mode
selection
0 to 4,6 to 8 0
"
""
""
""
""
""
"
Motor constants
80 Motor capacity
Set the motor capacity.
0.4kW to 55kW
Inverter
capacity
"
""
""
""
""
""
"
81
Number of motor
poles
Set the number of motor poles.
2,4,6
4
"
""
""
""
""
""
"
82
Motor excitation
current (no load
current)
Used for tuning data utilization or direct input. 9999
"
""
""
""
""
""
"
83 Rated motor voltage
Set the rated motor voltage.
0 to 1000V
200V
"
""
""
""
""
""
"
84
Rated motor
frequency
Set the rated motor frequency.
20 to 200Hz
60Hz
"
""
""
""
""
""
"
90 Motor constant R1
Used for tuning data utilization or direct input.
9999
"
""
""
""
""
""
"
91 Motor constant R2
9999
"
""
""
""
""
""
"
92 Motor constant L1
9999
"
""
""
""
""
""
"
93 Motor constant L2
9999
"
""
""
""
""
""
"
94 Motor constant X
9999
"
""
""
""
""
""
"
95
Online auto tuning
selection
0,1,2 0
"
""
""
""
""
""
"
96
Auto tuning setting/
status
Perform motor auto tuning when a motor other than SF-V5R,SF-VR,SF-JR or SF-
HRCA is used.
0,1,101
0
"
""
""
""
""
""
"
Third functions
110
Third acceleration/
deceleration time
Third function of acceleration/deceleration time set in Pr. 7, Pr. 8
0 to 3600/0 to 360s
5s
"
""
""
""
"
×
*
111
Third deceleration
time
Third function of deceleration time set in Pr. 8
0 to 3600/0 to 360s, 9999
9999
"
""
""
""
"
×
*
Output terminal
functions
116 Third speed detection
Set the speed at which the FB3 signal is output.
0 to 3600r/min
1500r/min
"
""
""
""
""
""
"
Function
Parameter
Name Outline
Factory
Setting
Cus-
tomer
Set-
ting
At-a-glance Guide to Func-
tions
"
""
": Usable function
×: Unusable function
* :
Functions that can be used
for parameter-set position con-
trol
Vector Control
Speed
control
Torque
control
Position
control
Pr. 75
Setting
Reset Selection
Disconnected
PU Detection
PU Stop
Selection
0 Reset input is always enabled.
If the PU is
disconnected,
operation will be
continued.
Pressing
decelerates the motor
to a stop only in the
PU operation mode.
1
Reset input is enabled only when
the protective function is activated.
2
Reset input is always enabled. When the PU is
disconnected, the
inverter output is
shut off.
3
Reset input is enabled only when
the protective function is activated.
14
Reset input is always enabled.
If the PU is
disconnected,
operation will be
continued.
Pressing
decelerates the motor
to a stop in any of the
PU, external and
communication
operation modes.
15
Reset input is enabled only when
the protective function is activated.
16
Reset input is always enabled. When the PU is
disconnected, the
inverter output is
shut off.
17
Reset input is enabled only when
the protective function is activated.
STOP
RESET
STOP
RESET