Mitsubishi Electronics FR-V500 Marine Battery User Manual


 
61
PARAMETERS
Function list (Extended function
parameters)
Maintenance
functions
168
Maker setting parameters. Do not make setting.
169
Initial
monitor
171
Actual operation hour
meter clear
You can clear the actual operation hour meter. 0
"
""
""
""
""
""
"
Terminal assignment functions
180
DI1 terminal function
selection
You can select the following input signals.
0: RL (multi-speed low-speed operation command) Pr. 180 factory setting
1: RM (multi-speed middle-speed operation command) Pr. 181 factory setting
2: RH (multi-speed high-speed operation command) Pr. 182 factory setting
3: RT (second function selection) Pr. 183 factory setting
5: JOG (jog operation selection)
8: REX (multi-speed 15 speeds selection)
9: X9 (third function selection)
10: X10 (FR-HC,FR-CV connection (inverter run enable signal))
11: X11 (FR-HC connection (instantaneous power failure detection)
12: X12 (PU operation external interlock)
14: X14 (PID control valid)
15: BRI (brake release completion signal)
16: X16 (PU operation-external operation switching)
20: X20 (S-pattern acceleration/deceleration C switching terminal)
22: X22 (orientation command)
23: LX (pre-excitation/servo on)
24:MRS(output stop)
25: STOP (start self-holding selection)
26: MC (control mode switching)
27: TL (torque restriction selection)
42: X42 (torque bias selection 1)
43: X43 (torque bias selection 2)
44: X44 (P control selection (P/PI control switching))
9999: No function (STR when set in Pr. 187)
0
"
""
""
""
""
""
"
181
DI2 terminal function
selection
1
"
""
""
""
""
""
"
182
DI3 terminal function
selection
2 "
""
""
""
""
""
"
183
DI4 terminal function
selection
3
"
""
""
""
""
""
"
187
STR terminal function
selection
9999
"
""
""
""
""
""
"
Terminal assignment functions
190
DO1 terminal function
selection
You can select the followin
g output signals.
0 (positive logic) Pr. 190 factory setting, 100 (negative logic): RUN (inverter running)
1 (positive logic) Pr. 191 factory setting, 101 (negative logic): SU (up to speed)
2 (positive logic) Pr. 192 factory setting, 102 (negative logic): IPF (instantaneous
power failure or undervoltage)
3 (positive logic), 103 (negative logic) : OL (overload alarm)
4 (positive logic), 104 (negative logic) : FU (output speed detection)
5 (positive logic), 105 (negative logic) : FU2 (second output speed detection)
6 (positive logic), 106 (negative logic) : FU3 (third output speed detection)
7 (positive logic), 107 (negative logic) : RBP (regenerative brake prealarm)
8 (positive logic), 108 (negative logic) : THP (electronic thermal alarm prealarm)
10 (positive logic), 110 (negative logic) : PU (PU operation mode)
11 (positive logic), 111 (negative logic) : RY (inverter operation ready)
12 (positive logic), 112 (negative logic) : Y12 (output current detection)
13 (positive logic), 113 (negative logic) : Y13 (zero current detection)
14 (positive logic), 114 (negative logic) : FDN (PID lower limit)
15 (positive logic), 115 (negative logic) : FUP (PID upper limit)
16 (positive logic), 116 (negative logic) : RL (PID forward/reverse rotation output)
20 (positive logic), 120 (negative logic) : BOF (brake opening request)
25 (positive logic), 125 (negative logic) : FAN (fan failure output)
26 (positive logic), 126 (negative logic) : FIN (fin overheat prealarm)
27 (positive logic), 127 (negative logic) : ORA (orientation completion)
30 (positive logic), 130 (negative logic) : Y30 (forward rotation output)
31 (positive logic), 131 (negative logic) : Y31 (reverse rotation output)
32 (positive logic), 132 (negative logic) : Y32 (regenerative status output)
33 (positive logic), 133 (negative logic) : RY2 (operation ready 2)
34 (positive logic), 134 (negative logic) : LS (low speed output)
35 (positive logic), 135 (negative logic) : TU (torque detection)
36 (positive logic), 136 (negative logic) : Y36 (in-position)
37 (positive logic), 137 (negative logic)) : MT (maintenance timer output)
40 (positive logic), 140 (negative logic) : Y40:(trace status)
41 (positive logic), 141 (negative logic) : FB (speed detection)
42 (positive logic), 142 (negative logic): FB2 (second speed detection)
43 (positive logic), 143 (negative logic) : FB3 (third speed detection)
44 (positive logic), 144 (negative logic) : RUN2 (second inveter operating)
96 (positive logic), 196 (negative logic): REM (remote output)
97 (positive logic), 197 (negative logic) : ER (minor fault output 2)
98 (positive logic), 198 (negative logic) : LF (minor fault output)
99 (positive logic) Pr. 195 factory setting, 199 (negative logic): ABC (alarm output)
9999: No function
0
"
""
""
""
""
""
"
191
DO2 terminal function
selection
1
"
""
""
""
""
""
"
192
DO3 terminal function
selection
2 "
""
""
""
""
""
"
195
A,B,C terminal
function selection
99
"
""
""
""
""
""
"
Function
Parameter
Name Outline
Factory
Setting
Cus-
tomer
Set-
ting
At-a-glance Guide to Func-
tions
"
""
": Usable function
×: Unusable function
* :
Functions that can be used
for parameter-set position con-
trol
Vector Control
Speed
control
Torque
control
Position
control