PARAMETERS
Parameter
5
Function list (Extended function
parameters)
Multi-speed operation
232
Multi-speed setting
(speed 8)
By setting any value other than "9999", set speeds 8 to 15.
This function is designed to change the running speed in stages by changing the ON/
OFF combination of the contact signals (RH, RM, RL, REX signals).
0 to 3600r/min, 9999
9999
"
""
""
""
"
×
*
233
Multi-speed setting
(speed 9)
9999
"
""
""
""
"
×*
234
Multi-speed setting
(speed 10)
9999
"
""
""
""
"
×*
235
Multi-speed setting
(speed 11)
9999
"
""
""
""
"
×
*
236
Multi-speed setting
(speed 12)
9999
"
""
""
""
"
×
*
237
Multi-speed setting
(speed 13)
9999
"
""
""
""
"
×
*
238
Multi-speed setting
(speed 14)
9999
"
""
""
""
"
×
*
239
Multi-speed setting
(speed 15)
9999
"
""
""
""
"
×
*
Sub functions
240 Soft-PWM setting
You can select to exercise Soft-PWM control and long wiring mode. When Soft-PWM
control is made valid, you can change the metallic tone of motor sound into an
unoffending complex tone. Surge voltage is surpressed in the long wiring mode
regardless of the wiring length between the inverter and motor. (When operating a
400V motor with wiring length of 40m or more, select long wiring mode.)
0: Soft-PWM control invalid, long wiring mode invalid
1: Soft-PWM control valid (when Pr. 72 = "1 or 2"), long wiring mode invalid
10: Soft-PWM control invalid, long wiring mode valid (carrier frequency is 2.25Hz *)
11: Soft-PWM control valid, long wiring mode valid (carrier frequency is 2.25Hz *)
*The Pr.72 "PWM frequency selection" setting is made invalid.
10
"
""
""
""
""
""
"
244
Cooling fan operation
selection
You can control the operation of the cooling fan built in the inverter.
0: The fan is always operated at power-on of the inverter.
1: The fan is always on while the inverter is running. During a stop, the inverter status is
monitored and the fan switches on-off according to the temperature.
0
"
""
""
""
""
""
"
Stop selection
function
250 Stop selection
Set to allow the motor to be coasted to a stop by turning off the start command during
V/F or speed control.
0 to 100s: Coasting to stop
9999: Deceleration to stop
9999
"
""
""
""
"
×
Operation selection
function
251
Output phase failure
protection selection
You can disable the output phase failure function that stops the inverter output if one of
the inverter output side (load side) three phases (U, V, W) opens.
0: Without output phase failure protection
1: With output phase failure protection
1
"
""
""
""
""
""
"
Additional
functions
252 Override bias
When you selected the override in Pr. 73, you can adjust the override bias (0 to 200%)
and override gain (0 to 200%).
50% "
""
""
""
"
×
253 Override gain
150%
"
""
""
""
"
×
Power failure stop functions
261
Power failure stop
selection
You can select the stopping method at a power failure.
0: Coasting to stop, inverter output shutoff
1: Inverter is decelerated to a stop.
0
"
""
""
""
"
×
262
Subtracted speed at
deceleration start
0 to 600r/min 90r/min
"
""
""
""
"
×
263
Subtraction starting
speed
0 to 3600r/min, 9999
1500r/min
"
""
""
""
"
×
264
Power-failure
deceleration time 1
0 to 3600/0 to 360s 5s
"
""
""
""
"
×
265
Power-failure
deceleration time 2
0 to 3600/0 to 360s, 9999 9999
"
""
""
""
"
×
266
Power-failure
deceleration time
switchover speed
0 to 3600r/min
1500r/min
"
""
""
""
"
×
Brake sequence
278 Brake opening speed
Set when outputting the operation timing signal of the mechanical brake in vertical lift
applications. (When speed control (invalid for V/F control) is selected)
0 to 900r/min (Pr. 278)
0 to 200% (Pr. 279)
0 to 2s (Pr. 280)
0 to 5s (Pr. 281)
0 to 900r/min (Pr. 282)
0 to 5s (Pr. 283)
0, 1 (Pr. 284)
0 to 900r/min, 9999 (Pr. 285)
20r/min
"
""
"
××
279
Brake opening
current
130%
"
""
"
××
280
Brake opening
current detection time
0.3s
"
""
"
××
281
Brake operation time
at start
0.3s
"
""
"
××
282 Brake operation speed
25r/min
"
""
"
××
283
Brake operation time
at stop
0.3s
"
""
"
××
284
Deceleration
detection function
selection
0
"
""
"
××
285
Overspeed detection
speed
9999
"
""
"
××
Function
Parameter
Name Outline
Factory
Setting
Cus-
tomer
Set-
ting
At-a-glance Guide to Func-
tions
"
""
": Usable function
×: Unusable function
* :
Functions that can be used
for parameter-set position con-
trol
Vector Control
Speed
control
Torque
control
Position
control
RH RM RL REX
Speed 8 OFF OFF OFF ON
Speed 9 OFF OFF ON ON
Speed 10 OFF ON OFF ON
Speed 11 OFF ON ON ON
Speed 12 ON OFF OFF ON
Speed 13 ON OFF ON ON
Speed 14 ON ON OFF ON
Speed 15 ON ON ON ON