Delta BLD-E1 Series Outboard Motor User Manual


 
Chapter 4 Parameters| BLD-E1 Series
Revision May 2009, 00DE, V0.50 4-65
06-0
2
Over-Current
Detection
Level
Output
Frequency
Over-Current Stall
prevention during
Acceleration,
frequency held
time
actual acceleration time when over-current stall
prevention is enabled
current
06-03
Over-current Stall Prevention during Operation
Control
mode
VF VFPG
Factory setting: 00
Settings 00: disable
00 to 250%
If the output current exceeds the setting specified in Pr.06-03 when the drive is operating, the
drive will decrease its output frequency by Pr.06-04 setting to prevent the motor stall. If the
output current is lower than the setting specified in Pr.06-03, the drive will accelerate (by
Pr.06-04) again to catch up with the set frequency command value.
Over-Current
Detection Level
06-03
Output Current
Output
Frequency
Over-Current Stall
Prevention during
Operation, output
frequency decrease
over-current stall prevention durin
g
operation
Time
06-04
Accel./Decel. Time Selection of Stall Prevention at constant speed
Control
mode
VF VFPG
Factory setting: 0
Settings 0 by current accel/decel time
1 by the 1st accel/decel time
2 by the 2nd accel/decel time
3 by the 3rd accel/decel time
4 by the 4th accel/decel time
5 by auto accel/decel time