Delta BLD-E1 Series Outboard Motor User Manual


 
Chapter 4 ParametersAT |Troubleshooting}| BLD-E1 Series
4-76
Revision May 2009, 00DE, V0.50
07-28
Emergency Stop (EF) & Forced Stop Selection
Control
mode
VF VFPG FOCPM
Factory Setting: 0
Settings 0 Coast to stop
1 By deceleration Time 1
2 By deceleration Time 2
3 By deceleration Time 3
4 By deceleration Time 4
5 By Pr.01-31
When the multi-function input terminal is set to 10 or 14 and it is ON, the brushless DC motor
drive will be operated by Pr.07-28.
07-29
Time for Decreasing Torque at Stop
Control
mode
FOCPM
Factory Setting: 0.000
Settings 0.000 to 1.000 sec
When the drive stop output it will produce the noise from the reacting force between the motor
and the mechanical brake. This parameter can be used to decrease this reacting force and
lower the noise.
It is used to set the time for decreasing torque to 0%.
RUN/STOP
0%
i
t
i
00-01
x
100%
300%
x
(07-29)=t