Group 10: Speed Feedback Control Parameters
: The parameter can be set during operation.
Paramete
r
Explanation Settings
Factory
Setting
VF VFPG FOCPM
10.00 Encoder Type 0:No function
1:ABZ
2:ABZ+UVW
3:AB+PWM
3 ○ ○
10.01 Encoder Pulse 1~25000 256 ○ ○
10.02 Encoder Input Type
Setting
0:Disable
0: Disable
1: Phase A leads in a forward run
command and phase B leads in
a reverse run command
2: Phase B leads in a forward
run command and phase A leads
in a reverse run command
3:Phase A is a pulse input and
phase B is a direction input.
(L=reverse direction, H=forward
direction)
1 ○ ○
10.03 Encoder Feedback
Fault Treatment
(PGF1, PGF2)
0: Warn and keep operation
1: Warn and decelerate to stop
2: Warn and stop operation
2 ○
10.04 Detection Time for
Encoder Feedback
Fault
0.0~10.0 sec 3.0 ○ ○
10.05 Encoder Stall Level
(PGF3)
0~120% (0:disable) 115 ○ ○
10.06 Encoder Stall
Detection Time
0.0~2.0 sec 0.1 ○ ○
10.07 Encoder Slip Range
(PGF4)
0~50% (0:disable) 50 ○ ○
10.08 Encoder Slip
Detection Time
0.0~10.0 sec 0.5 ○ ○