Paramete
r
Explanation Settings
Factory
Setting
VF VFPG FOCPM
Detection Time
(OT1)
06.08 Over-torque
Detection Selection
(OT2)
0: disable
1: over-torque detection during
constant speed operation, continue
to operate after detection
2: over-torque detection during
constant speed operation, stop
operation after detection
3: over-torque detection during
operation, continue to operate after
detection
4: over-torque detection during
operation, stop operation after
detection
0
06.09 Over-torque
Detection Level
(OT2)
10~250% 150
06.10 Over-torque
Detection Time
(OT2)
0.0~60.0 sec 0.1
06.11 Current Limit 0~250% 200
06.12 Electronic Thermal
Relay Selection
0: Inverter motor
1: Standard motor
2: Disable
2
06.13 Electronic Thermal
Characteristic
30.0~600.0 sec 60.0
06.14 Heat Sink Over-
heat (OH) Warning
0.0~110.0 85.0
06.15 Stall Prevention
Limit Level
0100% (refers to Pr. 06-02, 06-03) 50
06.16 Present Fault
Record
0: No fault
0
06.17 Second Most 1: Over-current during acceleration 0