It is used to set the accel./decel. time selection when stall prevention occurs at constant
speed.
06-05
Over-torque Detection Selection (OT1)
Control
mode
VF VFPG FOCPM
Factory setting: 0
Settings 0 Over-Torque detection disabled.
1 Over-torque detection during constant speed operation, continue to
operate after detection
2 Over-torque detection during constant speed operation, stop
operation after detection
3 Over-torque detection during operation, continue to operate after
detection
4 Over-torque detection during operation, stop operation after
detection
06-06
Over-torque Detection Level (OT1)
Control
mode
VF VFPG FOCPM
Factory setting: 150
Settings 10 to 250%
06-07
Over-torque Detection Time (OT1)
Control
mode
VF VFPG FOCPM
Factory setting: 0.1
Settings 0.0 to 60.0 sec
06-08
Over-torque Detection Selection (OT2)
Control
mode
VF VFPG FOCPM
Factory setting: 0
Settings 0 Over-Torque detection disabled.
1 Over-torque detection during constant speed operation, continue to
operate after detection
2 Over-torque detection during constant speed operation, stop
operation after detection
3 Over-torque detection during operation, continue to operate after
detection
4 Over-torque detection during operation, stop operation after
detection
06-09
Over-torque Detection Level (OT2)
Control
mode
VF VFPG FOCPM
Factory setting: 150
Settings 10 to 250%