Schneider Electric Altivar 12 Outboard Motor User Manual


 
42 BBV28581 05/2010
Monitoring mode MOn
Code
Name/Description Unit
MAI-
Maintenance menu (continued)
rtHI
M Run elapsed time display
0.01
Total time the motor has been powered up. Range: 0 to 65535 hours. Value displayed is as described in the
table below. Parameter resettable by services
Hours Display
1 0.01
10 0.10
100 1.00
1000 10.0
10000 100
PtH
M Power On time display
0.01
Total time the drive has been powered on. Range: 0 to 65535 hours. Value displayed is as described in
the table above. Parameter resettable by services.
FtH
M Fan time display
0.01
Range: 0 to 65535 hours. Value displayed is as described in the table above. Parameter resettable by
customer.
PEt
M Process elapsed time
0.01
T
Range: 0 to 65535 hours. Value displayed is as described in the table above. Parameter resettable by
customer.
COM1
M Modbus communication status
-
r0t0
rOt1
r1t0
r1t1
v Modbus no reception, no transmission = communication idle
v Modbus no reception, transmission
v Modbus reception, no transmission
v Modbus reception and transmission
dP1
M Last detected fault 1
-
This parameter describes the last detected fault.
EP1
M State of drive at detected fault 1
-
This parameter describes the state at the moment of the 1st detected fault.
bit 0 bit 1 bit 2 bit 3 bit 4
ETA.1: Switched
on
ETA.5:
Quick stop
ETA.6:
Switch on
disabled
Forced local
enabled
ETA.15 :
Motor rotation in forward direction
(or stopped)
bit 5 bit 6 bit 7 bit 8 bit 9
ETI.4: Run order
present
ETI.5:
DC injection
running
ETI.7:
Motor thermal
threshold reached
ETI.8: Reserved ETI.9:
Product in
acceleration
bit 10 bit 11 bit 12 bit 13 - 14 bit 15
ETI.10 : Product in
deceleration
ETI.11 : Current
limitation or torque
limitation is
running
Fast stop in
progress
ETI.14= 0 + ETI.13=0 :
Drive controlled by terminal or local
keypad
ETI.14= 0 + ETI.13=1 :
Drive controlled by remote keypad
ETI.14= 1 + ETI.13=0 :
Drive controlled by Modbus
ETI.14= 1 + ETI.13=0 : Reserved
ETI.15 :
Reverse
direction
applied to the
ramp
T
Parameter that can be modified during operation or when stopped.