BBV28581 05/2010 77
Configuration Mode - Complete menu (FULL)
Code
Name/Description Adjustment range Factory setting
FUn-
Function menu (continued)
PId-
PID menu (continued)
PMP-
Pump sub-menu
tOL
M Application Overload time delay
0 to 100 s 0 s
See page 54
Visible only if PID feedback assignment PIF page 72 is not set to nO.
LOC
T
M Application Overload threshold
70 to 150% of nCr 90%
See page 54
Visible only if Application Overload time delay tOL above is not set to nO.
FtO
T
M Time delay before automatic start for the
overload fault
0 to 6 min 0 min
If Atr = YES the drive restarts automatically after an overload fault OLC once this time delay has
elapsed.
Minimum time permitted between an overload being detected and any automatic restart.
In order for an automatic restart to be possible, the value of Maximum restart time tAr page 91
must
exceed that of this parameter by at least one minute.
Visible only if Application Overload time delay tOL above is not set to nO.
ULt
M Application underload time delay
0 to 100 s 0 s
See page 55
Visible only if PID feedback assignment PIF page 72 is not set to nO.
LUL
T
M Application Underload threshold
20 to 100% of nCr 60%
See page 55
Visible only if Application underload time delay ULt above is not set to nO.
T
Parameter that can be modified during operation or when stopped.