Configuration Mode - Complete menu (FULL)
Code
Name/Description Adjustment range Factory setting
I_O-
Input Output menu
tCC
M Type of control
2C
2C
3C
v 2-wire control (see page 51)
The open or closed state of the input controls the running or stopping.
Example of "source" wiring:
LI1: forward
LIx: reverse
v 3-wire control (see page 51)
"forward" or "reverse" pulse is sufficient to command starting, a "stop" pulse is sufficient to command
stopping
Example of "source" wiring:
LI1: stop
LI2: forward
LIx: reverse
DANGER
UNINTENDED EQUIPMENT OPERATION
When this parameter is changed, 2 wire type control tCt page 51 and all the assignments involving the logic
inputs will revert to their default values.
Check that this change is compatible with the wiring diagram used.
Failure to follow these instructions will result in death or serious injury.
To change the assignment of this parameter press the “ENT” key for 2 s.
I-O-
drC-
CtL-
FUN-
FLt-
COM-
2 s
2 s