Schneider Electric Altivar 12 Outboard Motor User Manual


 
BBV28581 05/2010 47
Configuration Mode - Complete menu (FULL)
Code
Name/Description Adjustment range Factory setting
CFG
M Macro-configuration
StS
DANGER
UNINTENDED EQUIPMENT OPERATION
Check that the selected macro configuration is compatible with the wiring diagram used.
Failure to follow these instructions will result in death or serious injury.
StS
PId
SPd
Macro configuration provides a shortcut to configure a set of parameters suited to a specific field of
application.
3 macro configurations are available:
v Start/stop. Only forward is assigned
v PID regulation. Activate PID function, dedicated AI1 for feedback and AIV1 for reference.
v Speed. Allocate LI to preset speed (same allocation as ATV11) which provides a means of speeding up
the configuration of functions for a specific field of application.
Selecting a macro configuration assigns the parameters in this macro configuration.
Each macro configuration can still be modified in the other menus.
To change the assignment of this parameter press the “ENT” key for 2 s.
2 s
Input / output or parameter
Start / Stop PID regulation Speed
AI1 Ref. channel 1 PID feedback No
AIV1 No Reference channel 1
AO1 No
LO1 No
R1 No drive detected fault
L1h (2-wire) Forward
L2h (2-wire) No Reverse
L3h (2-wire) No Auto/Manu 2 preset speeds
L4h (2-wire) No 4 preset speeds
L1h (3-wire) Stop
L2h (3-wire) Forward
L3h (3-wire) No Reverse
L4h (3-wire) No Auto / Manu 2 preset speeds
Fr1 (Reference channel 1)
AIUI AIUI
Ctt (Motor control type)
PUMP
rIn (Reverse inhibition)
YES
AI1t (AI1t type)
0A
LFLl (4-20 mA loss)
YES
SP2 (Preset speed 2)
10.0
SP3 (Preset speed 3)
25.0
SP4 (Preset speed 4)
50.0
MPC (Motor parameter choice)
COS
AdC (Automatic DC injection)
YES YES YES
2 s