Configuration Mode - MyMenu
How to control the drive locally
In factory settings "RUN" and the jog dial are inactive. To control the drive locally, adjust the following parameter:
set Reference channel 1 Fr1 page 45
to AIU1 (Integrated display with jog dial).
LI assignment information
It is possible with ATV12 to use multi assignment function (ie: AC2 and rrS on the same LI).
It is also possible on some functions to assign LIH (high) or LIl (low), which means that the assigned function will be activated to high (LIH)
or low level (LIl) of LI.
Code
Name/Description Adjustment range Factory setting
nPr
M Rated Motor Power
NCV -5 to
NCV +2
According to drive
rating
Visible only if Motor parameter choice MPC page 60 is set to nPr. If nPr is available CoS disappears.
Rated motor power given on the nameplate. Motors can range from five ratings lower up to two ratings
higher than the drive rating.. Performance is optimized when there is a maximum of one rating difference.
If Standard motor frequency bFr page 45
is set to 50Hz, the Rated motor power nPr unit will be kW,
otherwise it will be HP.
SCS
M Store customer parameter set
nO
nO
Str1
This function creates a backup of the present configuration:
v Function inactive
v Saves the current configuration in the drive memory. SCS automatically switches to nO as soon as the
save has been performed.
When a drive leaves the factory the current configuration and the backup configuration are both initialized
with the factory configuration.
FCS
M Factory / recall customer parameter set
nO
nO
rEC1
InI
InI1
This function permits to restore a configuration.
v Function inactive.
FCS automatically changes to nO as soon as one of the following actions has been performed.
v The current configuration becomes identical to the backup configuration previously saved by SCS.
FCS automatically changes to nO
as soon as this action has been performed. rEC1 is only visible
if the backup has been carried out. If this value appears, InI1 is not visible.
v The current configuration becomes identical to the factory setting. If this value appears, InI1 is not
visible.
v The current configuration becomes identical to the backup configuration previously defined by SoMove
software. If this value appears, Ini and rEC1 are not visible.
DANGER
UNINTENDED EQUIPMENT OPERATION
Check that the modification of the current configuration is compatible with the wiring diagram used.
Failure to follow these instructions will result in death or serious injury.
To change the assignment of this parameter press the “ENT” key for 2 s.
2 s
2 s
2 s