Configuration Mode - Complete menu (FULL)
Code
Name/Description Adjustment range Factory setting
FUn-
Function menu (continued)
rPt-
Ramp menu (continued)
AC2
T
M Acceleration 2
0.0 to 999.9 s 5.0 s
Visible only if Ramp switching commutation rPS page 64 is not set to nO.
Second acceleration ramp time, adjustable from 0.0 to 999.9 s
This ramp will be the active ramp when using PID for the start and wake-up phases only, see PID wake up
level page 75
.
dE2
T
M Deceleration 2
0.0 to 999.9 s 5.0 s
Visible only if Ramp switching commutation rPS page 64 is not set to nO.
Second deceleration ramp time, adjustable from 0.0 to 999.9 s
brA
M Decel Ramp Adaptation assignment
YES
nO
YES
dYnA
v Function inactive. The drive will decelerate based on the normal deceleration adjustment. This setting is
compatible with optional dynamic braking if used.
v This function automatically increases deceleration time when stopping or reducing the speed of high inertia
loads to help prevent DC bus overvoltage or overbraking.
v Motor Braking: This mode allows the drive to attempt the most rapid stop possible without the use of a
dynamic brake resistor. It uses motor losses to dissipate energy from regeneration. This function may be
incompatible with positioning. This function should not be used when an optional braking resistor and
module are being used.
Attention: When using a braking resistor set brA to nO.
T
Parameter that can be modified during operation or when stopped.