Schneider Electric Altivar 12 Outboard Motor User Manual


 
80 BBV28581 05/2010
Configuration Mode - Complete menu (FULL)
Architecture of the pumping installation
Single variable mode - 1 single variable speed pump
Enter the values given on the motor rating plate in the Motor control menu drC
1st level adjustment parameters
ACC Acceleration: 0.7 s
dEC Deceleration: 0.7 s
LSP Low speed: 30 Hz
HSP High speed: 60 Hz
Analog input menu AIt
AI1t Scale of analog input AI1: 0-20 mA
Motor control menu drC
SLP Nominal motor slip: 0 Hz
FLG Frequency loop gain: 70%
UFr IR compensation: 0%
Application functions menu FUn
tCt 2-wire type control: LEL
PI sub-menu
PIF Assignment of the PI function feedback: AI1
rPG PI regulator proportional gain: 5.00
rIG PI regulator integral gain: 8.00
rPI Internal PI regulator reference: 39%
rSL Restart error threshold: 40%
MPI Supervision of the PI regulator function: LFF
LPI PI feedback supervision threshold: 17%
tPI PI feedback supervision function time delay: 1 s
LFF Fallback speed: 50 Hz
Pump sub-menu PMP
nFd Zero flow detection: 1 min
FFd Zero flow detection activation threshold: 50 Hz
LFd Zero flow detection offset: 5 Hz
tLS Sleep threshold operating time: 3 s
SFS Quick start threshold: 25 Hz
SLE Sleep threshold offset: 10 Hz
Automatic DC injection sub-menu AdC
AdC Automatic DC injection assignment: nO
Automatic restart function Atr
Atr Automatic restart: YES
Fault menu FLt
LOC Overload threshold: 11%
FtO Time delay before automatic start for the overload fault: 1
Ap0 Frequency hysteresis reached: 2 kHz
Variable pump
ATV12
Pressure sensor
0-20 mA
4-20 mA
0+5 V
0+10 V