Code
Name/Description Adjustment range Factory setting
FUn-
Function menu (continued)
PId-
PID menu (continued)
LPI
T
M PI feedback supervision threshold
nO to 100% nO
An alarm can be assigned to a relay or a logic output.
Adjustment range:
v No: Function inactive (it will not be possible to access the other function parameters)
v between minimum and maximum PID feedback.
Visible only if PID feedback assignment PIF page 72
is not set to nO.
tPI
T
M PI feedback supervision function time delay
0 to 600 s 0 s
Visible only if PI feedback supervision threshold LPI above is not set to nO.
AP0
T
M Maximum frequency detection hysteresis
0 to HSP 0 Hz
Visible only if PI feedback supervision threshold LPI above is not set to nO.
MPI
M PI feedback supervision
YES
Fallback mode for the PI feedback supervision function.
v YES: freewheel stop
v LFF: switch to fallback speed LFF as long as the fault is present and the run command is not disabled.
Visible only if PI feedback supervision threshold LPI above is not set to nO.
LFF
M Fallback speed
0 to HSP 0 Hz
Fallback speed for PID regulator feedback supervision fault.
T
Parameter that can be modified during operation or when stopped.