Schneider Electric Altivar 12 Outboard Motor User Manual


 
BBV28581 05/2010 73
Configuration Mode - Complete menu (FULL)
Code
Name/Description Adjustment range Factory setting
FUn-
Function menu (continued)
PId-
PID menu (continued)
Pr4
M 4 preset PID assignment
nO
nO
L1H
L2H
L3H
L4H
Visible only if PID feedback assignment PIF page 72 is not set to nO.
v No
v L1h
v L2h
v L3h
v L4h
2 preset PID assignment Pr2 page 72
must be assigned before assigning 4 preset PID assignment
Pr4.
rP2
T
M 2 preset PID reference
0 to 100% 25%
Visible only if PID feedback assignment PIF page 72 and 2 preset PID assignment Pr2 page 72 are
not set to nO.
rP3
T
M 3 preset PID reference
0 to 100% 50%
Visible only if PID feedback assignment
?
PIF page 72 and 4 preset PID assignment Pr4 page 72 are
not set to nO.
rP4
T
M 4 preset PID reference
0 to 100% 75%
Visible only if PID feedback assignment PIF page 72 and 2 preset PID assignment Pr2 and 4 preset
PID assignment Pr4 page 72
are not set to nO.
rPI
T
M Internal PID reference
0 to 100% 0%
Visible only if PID feedback assignment PIF page 72 is not set to nO and if Activation internal PID
reference PII page 72
is set to YES or Reference channel 1 Fr1 page 45 is set to LCC.
PrP
T
M PID reference ramp
0 to 100% 0%
Visible only if PID feedback assignment PIF page 72 is not set to nO.
rPL
T
M PID min value reference
0 to 100% 0%
Visible only if PID feedback assignment PIF page 72 is not set to nO.
rPH
T
M PID max value reference
0 to 100% 100%
Visible only if PID feedback assignment PIF page 72 is not set to nO
SFS
M PID predictive speed
0.1 to 400 Hz nO
This parameter allows to go directly to a set speed reference.
Visible only if PID feedback assignment PIF page 72
is not set to nO.
T
Parameter that can be modified during operation or when stopped.