BBV28581 05/2010 97
Configuration Mode - Complete menu (FULL)
Code
Name/Description Adjustment range Factory setting
COM-
Communication menu
Note: For following parameters, the modifications will be taken into account only at the next control power on.
Add
M Modbus address
OFF to 247 OFF
Modbus address is adjustable from OFF to 247. When OFF, communication is not active.
tbr
M Modbus baud rate
19.2
4.8
9.6
19.2
38.4
v 4.8 kbps
v 9.6 kbps
v 19.2 kbps
v 38.4 kbps
tFO
M Modbus format
8E1
8o1
8E1
8n1
8n2
v 8o1
v 8E1
v 8N1
v 8N2
ttO
M Modbus time out
0.1 to 30 s 10 s
The drive detects a Modbus fault if it does not receive any Modbus request at its address within a
predefined time period (time out).
ICS-
Input scanner menu (values are expressed in hexadecimal)
nMA1
M Com scanner read address parameter 1
0C81
Address of the 1st input word.
nMA2
M Com scanner read address parameter 2
219C
Address of the 2nd input word.
nMA3
M Com scanner read address parameter 3
0
Address of the 3rd input word.
nMA4
M Com scanner read address parameter 4
0
Address of the 4th input word.
OCS-
Output scanner menu (values are expressed in hexadecimal)
nCA1
M Com scanner write address parameter 1
2135
Address of the 1st output word.
nCA2
M Com scanner write address parameter 2
219A
Address of the 2nd output word.
nCA3
M Com scanner write address parameter 3
0
Address of the 3rd output word.
nCA4
M Com scanner write address parameter 4
0
Address of the 4th output word.