Schneider Electric Altivar 12 Outboard Motor User Manual


 
52 BBV28581 05/2010
Configuration Mode - Complete menu (FULL)
Code
Name/Description Adjustment range Factory setting
I_O-
Input Output menu (continued)
AI1-
AI1 configuration menu
AI1t
M AI1 type
5U
5U
10U
0A
This function makes interface from the analog input signal to a drive internal value.
v Voltage: 0-5 Vdc
v Voltage: 0-10 Vdc
v Current: x-y mA. Range determined by the AI1 current scaling parameter of 0% CrL1 and AI1 current
scaling parameter of 100% CrH1 settings below, see page 52
.
CrL1
M AI1 current scaling parameter of 0%
0 to 20 mA 4 mA
Visible only if AI1 type AI1t is set to 0A
CrH1
M AI1 current scaling parameter of 100%
0 to 20 mA 20 mA
Visible only if AI1 type AI1t is set to 0A
I_O-
Input Output menu (continued)
r1
M R1 assignment
FLt
nO
FLt
rUn
FtA
FLA
CtA
SrA
tSA
ULA
OLA
AP1
v Not assigned
v No error detected
v Drive run
v Frequency threshold reached
v HSP reached
v I threshold reached
v Frequency reference reached
v Motor thermal reached
v Underload alarm
v Overload alarm
v AI1 Al. 4-20 - Visible only if AI1t is set to 0A (see above)