HP (Hewlett-Packard) E1412A Waterskis User Manual


 
Measurement Speed and Accuracy Trade-offs 195Appendix C
HP E1312A/E1412A Resolution Using Special Functions
and Ranges
Resolution remains a function of the NPLC parameter set at the time a
special function or range is used. The NPLC setting is fixed throughout use
of the special functions and ranges unless you change the setting with the
[SENSe:]<function>:NPLC command or configure the multimeter with the
CONFigure command using a resolution that changes the NPLC setting. The
resolution will track the NPLC setting as shown in Tables 3-1, 3-2, and 3-3
beginning on page 70.
The following table shows range and NPLC settings for power-on and after
a module reset. Changing a range within one function does not place other
functions at that range setting. Each function operates independently.
Note Refer to Tables 3-1, 3-2 and 3-3 in Chapter 3, to determine what resolution
will result following a special function or special range change. The NPLC
setting remains fixed for each function during execution of the special
function and range commands (e.g., may differ from function to function).
Resolution Example Assume the power-on state where the multimeter function is DC Voltage,
10V range, with an NPLC setting of 10 PLCs providing 10
µ
V resolution
(see Table 3-1 on page 70). Use the special range command R5 to change
the DC Voltage range to 300V. The NPLC setting remains at 10 PLCs
providing a resolution of 1mV (see Table 3-1 on page 70).
Use the special function command
F3 to change the function to 2-Wire
Resistance. The range goes to the resistance power-on state (1k
for 2-Wire
Resistance, NPLC = 10); it does not change with the previous
DCV R5
command. NPLC remains at 10 PLCs providing resolution of 1m
.
The special range commands do not affect other functions except in the
F3
(
RES) and F4 (FRES) function changes. Range changes on F3 cause the
same range change on
F4 and vice versa.
Special Function
HP E1312A/E1412
Power-on State
HP E1312A/E1412
*RST State
F1 10V (R3), NPLC = 10 300V (R5), NPLC = 10
F2 1A (R3), NPLC = 10 1A (R3), NPLC = 10
F3 1k (R2), NPLC = 10 1k (R2), NPLC = 10
F4 1k (R2), NPLC = 10 1k (R2), NPLC = 10