Hitachi L200 Marine Battery User Manual


 
L200 Inverter
Configuring
Drive Parameters
3–39
“B” Function
Run
Mode
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FEF
(EU)
–FU
(USA)
Units
B032 Reactive current setting Calibrate detection of motor’s
reactive (no load) current for
current monitor, electric
thermal setting, and overload
restriction setting.
Range is 50 to 200%
100. 100. %
Io-SET 00100%
B080 [AM] analog signal
gain
Adjust of analog output at
terminal [AM],
range is 0 to 255
100. 100.
AM-Adj 00100%
B082 Start frequency adjust-
ment
Sets the starting frequency for
the inverter output, range is 0.5
to 9.9 Hz
0.5 0.5 Hz
fmin 0000.5Hz
B083 Carrier frequency
setting
Sets the PWM carrier (internal
switching frequency), range is
2.0 to 14.0 kHz
5.0 5.0 kHz
Carrier 0005.0
B084 Initialization mode
(parameters or trip
history)
Select the type of initialization
to occur, two option codes:
00...Trip history clear
01...Parameter initialization
02...Trip history clear and
parameter initialization
00 00
INIT Mode TRP
B085 Country code for initial-
ization
Select default parameter values
for country on initialization,
four options, option codes:
00...Japan version
01...Europe version
02...US version
01 02
INIT Slct USA
B086 Frequency scaling
conversion factor
Specify a constant to scale the
displayed frequency for D007
monitor, range is 0.1 to 99.9
1.0 1.0
Cnv Gain 0001.0
B087 STOP key enable Select whether the STOP key
on the keypad is enabled, two
option codes:
00...enabled
01...disabled
00 00
STP Key ON