Hitachi L200 Marine Battery User Manual


 
Introduction
Appendix B
B–2
Introduction
L200 Series inverters have built-in RS-485 serial communications, featuring the
ModBus RTU protocol. The inverters can connect directly to existing factory networks
or work with new networked applications, without any extra interface equipment. The
specifications for L200 serial communications are in the following table.
The network diagram below shows a series of inverters communicating with a host
computer. each inverter must have a unique address, from 1 to 32, on the network. In a
typical application, a host computer or controller is the master and each of the inverter(s)
or other devices is a slave.
Item Specifications User-selectable
Transmission speed 4800 / 9600 / 19200 bps
Communication mode Asynchronous
Character code Binary
LSB placement Transmits LSB first
Electrical interface RS-485 differential transceiver
Data bits 8-bit (ModBus RTU mode) (ASCII mode not
available)
Parity None / even / odd
Stop bits 1 or 2 bits
Startup convention One-way start from host device
Wait time for response 0 to 1000 msec.
Connections Station address numbers from 1 to 32
Connector RJ45 modular jack
Error check Overrun, Fleming block check code,
CRC-16, or horizontal parity
L200
1
2
RUN
STOP
RESET
FUNC.
STR
HITACHI
POWER
ALARM
RUN
A
Hz
PRG
5 0.0
L200
1
2
RUN
STOP
RESET
FUNC.
STR
HITACHI
POWER
ALARM
RUN
A
Hz
PRG
5 0.0
L200
1
2
RUN
STOP
RESET
FUNC.
STR
HITACHI
POWER
ALARM
RUN
A
Hz
PRG
5 0.0
1
ModBus Network
232
Host computer