Hitachi L200 Marine Battery User Manual


 
“A” Group: Standard Functions
Configuring
Drive Parameters
3–12
The inverter has other control sources that can temporarily override the parameter A001
setting, forcing a different output frequency source. The following table lists all
frequency source setting methods and their relative priority (“1” is the highest priority).
The inverter also has other control sources that can temporarily override the parameter
A002 setting, forcing a different Run command source. The following table lists all Run
command setting methods and their relative priority (“1” is the highest priority).
Priority A001 Frequency Source Setting Method Refer to page...
1 [CF1] to [CF4] Multi-speed terminals
4–13
2 [OPE] Operator Control intelligent input
4–31
3 [F-TM] intelligent input
4–33
4 [AT] terminal
4–23
5 TM/PRG DIP Switch - (if switch is in “TM” position)
3–11
6 A001 Frequency source setting
3–10
Priority A002 Run Command Setting Method Refer to page...
1 [OPE] Operator Control intelligent input
4–31
2 [F-TM] intelligent input
4–33
3 TM/PRG DIP Switch - (if switch is in “TM” position)
3–11
4 A002 Run command source setting
3–10