Hitachi L200 Marine Battery User Manual


 
L200 Inverter
Appendix B
B–37
C042 Frequency arrival
setting for acceleration
R/W Sets the frequency arrival
setting threshold for the output
frequency during acceleration,
range is 0.0 to 400.0 Hz
00BCh 0 to 4000
*1
0.1 Hz
C043 Arrival frequency
setting for deceleration
R/W Sets the frequency arrival
setting threshold for the output
frequency during deceleration,
range is 0.0 to 400.0 Hz
00BDh 0 to 4000 0.1 Hz
C044 PID deviation level
setting
R/W Sets the allowable PID loop
error magnitude (absolute
value), SP - PV, range is 0.0 to
100%, resolution is 0.1%
00BEh 0 to 1000 0.1 %
C052 PID FBV function high
limit
R/W When the PV exceeds this
value, the PID loop turns OFF
the PID Second Stage Output,
range is 0.0 to 100.0%
00EAh 0 to 1000 0.1 %
C053 PID FBV function low
limit
R/W When the PV goes below this
value, the PID loop turns ON
the PID Second Stage Output,
range is 0.0 to 100.0%
00EBh 0 to 1000 0.1 %
C071 Communication speed
selection
NOTE: These network settings
are not accessible to ModBus.
Use the inverter keypad or
digital operator to edit. Refer to
“Network Communication
Settings” on page 3–51.
00C0h
C072 Node allocation 00C1h
C074 Communication parity
selection
00C3h
C075 Communication stop bit
selection
00C4h
C076 Communication error
select
00ECh
C077 Communication error
time-out
—00EDh
C078 Communication wait
time
00C5h
C081 O input span calibration R/W Scale factor between the
external frequency command
on terminals L – O (voltage
input) and the frequency
output, range is 0.0 to 200.0%
00C7h 0 to 2000 0.1 %
C082 OI input span calibra-
tion
R/W Scale factor between the
external frequency command
on terminals L – OI (current
input) and the frequency
output, range is 0.0 to 200.0%
00C8h 0 to 2000 0.1 %
“C” Group Intelligent Terminal Functions
Func.
Code
Name R/W Description
Network Data
Reg. Range Res.