Chapter 11—Multi-tariff feature PowerLogic™ PM5500 series user manual
Configuring tariffs
This section explains how to set up tariffs.
You can change the tariff mode using the front panel.
When the meter is set to command mode for tariffs, the active tariff is controlled by
Modbus commands sent from your energy management system or other Modbus
master.
Related topics
Search your meter’s Modbus register list at www.schneider-electric.com to
download the Modbus map.
Configuring time of day mode tariffs
When the meter is set to time of day for tariffs, the active tariff is determined by the day
type, the start and end times, and the start and end dates. The time of day tariff is not a
calendar; the meter does not calculate the corresponding day of the week to a specific
date, but February 29th is considered a valid date if you are programming the meter
during a leap year.
When you enter tariff times using the front panel, be aware that the displayed minute
value includes the entire minute. For example, an end time of 01:15 includes the time
from 01:15:00 through 01:15:59. To create a tariff period that starts right after this, you
must set the next tariff’s start time to 01:16. Although it may appear that there is a gap
between these tariffs, there is not.
NOTE: You must always set the tariff times to UTC (GMT, Greenwich Mean Time), not
local time. The GMT Offset (h) setup parameter does not apply to tariff times.
Use ION Setup to configure time of day mode tariffs.
Related topics
See “Meter configuration using ION Setup” on page 51 to configure the tariffs and
other parameters using ION Setup.
Configuring input mode tariffs using the front panel
When you set the tariff type to Input, the active tariff is determined by the status of the
digital inputs.
T50101
T60110
T70111
T8
2
1000
1
This digital input configuration (0000) means there are no active tariffs (all tariffs are disabled)
2
Any configuration above 8, i.e., 1001 and higher, is invalid and therefore ignored by the meter (the active tariff
does not change).
Configuration 2: 8 tariff assignment using 4 digital inputs (Continued)
Tariff setup menu tree
Maint
Reset
Setup Basic
Adv
Dmd
Tariff
Meter