Schneider Electric HRB1684301-01 Marine Instruments User Manual


 
PowerLogic™ PM5500 series user manual Chapter 8—Input / Output
HRB1684301-01 77
Configuring digital outputs using ION Setup
You can use ION Setup to configure the digital outputs (D1 and D2).
1. Start ION Setup.
2. Connect to your meter
3. Navigate to I/O configuration > I/O Setup.
4. Select a digital output to configure and click Edit. The setup screen for that digital
output is displayed.
5. Enter a descriptive name for the digital output’s Label.
6. Configure the other setup parameters as required.
7. Click Send to save your changes.
Digital output setup parameters available through ION Setup
Parameter Values Description
Label
Use this field to change the default label and assign a
descriptive name to this digital output.
Control Mode
External, Demand Sync,
Alarm, Energy
This field displays how the digital output functions.
External: the digital output is controlled remotely
either through software or by a PLC using
commands sent through communications.
Demand Sync: the digital output is associated
with one of the demand systems. The meter
sends a pulse to the digital output port at the end
of every demand interval.
Alarm: the digital input is associated with the
alarm system. The meter sends a pulse to the
digital output port when the alarm is triggered.
Energy: The digital output is associated with
energy pulsing. When this mode is selected, you
can select the energy parameter and the set the
pulse rate (pulses/kW).
Behavior Mode Normal, Timed, Coil Hold
Normal: this mode applies when control mode is
set to External or Alarm. The digital output
remains in the ON state until an OFF command is
sent by the computer or PLC.
Timed: the digital output remains ON for the
period defined by the On Time setup register.
Coil Hold: this mode applies when control mode
is set to External or Alarm. For a unary alarm that
is associated with a digital output, you must set
Behavior Mode to Coil Hold. The output turns on
when the “energize” command is received and
turns off when the “coil hold release” command is
received. In the event of a control power loss, the
output remembers and returns to the state it was
in when control power was lost.
On Time (s) 0 to 9999
This setting defines the pulse width (ON time) in
seconds.
Select Dmd System
Power, Current, Input
Metering
Applies when Control Mode is set to Demand Sync.
Select the demand system to monitor.