Schneider Electric HRB1684301-01 Marine Instruments User Manual


 
PowerLogic™ PM5500 series user manual Chapter 8—Input / Output
HRB1684301-01 81
5. Press or to modify the parameter as required, then press OK.
6. Press to exit. Press Yes to save your changes.
Configuring the LED or digital output for energy pulsing using
ION Setup
You can use the ION Setup to configure your meter’s LED or digital output for energy
pulsing.
1. Start ION Setup.
2. Connect to your meter
3. Navigate to I/O configuration > Energy Pulsing.
4. Select the LED or a digital output to configure and click Edit. The setup screen is
displayed.
5. Enter a descriptive name for the digital output’s Label.
6. Configure the other setup parameters as required.
7. Click Send to save your changes.
Related topics
See “Alarm display and notification” on page 102 for details on using the front panel
to view and acknowledge alarms.
See “Alarm priorities” on page 96 for a detailed description on the alarm / energy
pulsing LED’s behavior when it is configured for alarm notification.
Alarm / energy pulsing LED setup parameters
Setting Option or range Description
Mode Disabled, Alarm, Energy
Disabled turns off the LED completely.
Alarm sets the LED for alarm notification.
Energy sets the LED for energy pulsing.
Parameter
Active Del,
Active Rec,
Active Del + Rec,
Reactive Del,
Reactive Rec,
Reactive Del + Rec,
Apparent Del,
Apparent Rec,
Apparent Del + Rec
Select which accumulated energy channel to monitor and
use for energy pulsing. This setting is ignored when the
LED mode is set to Alarm.
Pulse Wt. (p/k_h) 1 to 9999999
When configured for energy pulsing, this setting defines
how many pulses are sent to the LED for every 1 kWh,
1 kVARh or 1kVAh accumulated energy. This setting is
ignored when the LED mode is set to Alarm.
Alarm / energy pulsing LED setup parameters available through ION Setup
Parameter Values Description
Mode Off, Alarm, Energy
Off disables the LED.
Alarm sets the LED for alarm notification.
Energy sets the LED for energy pulsing.
Pulse Wt. (p/k_h) 1 to 9999999
When configured for energy pulsing, this
defines how many pulses are sent to the LED
for every 1 kWh, 1 kVARh or 1kVAh of
accumulated energy.
Channel
Active Energy Delivered,
Active Energy Received,
Active Energy Del+Rec,
Reactive Energy Delivered,
Reactive Energy Received,
Reactive Energy Del+Rec,
Apparent Energy Delivered,
Apparent Energy Received
Apparent Energy Del+Rec
Select which accumulated energy channel to
monitor and use for energy pulsing.