Schneider Electric HRB1684301-01 Marine Instruments User Manual


 
PowerLogic™ PM5500 series user manual Chapter 5—Meter webpages
HRB1684301-01 55
User setup
To set up users for the webpages:
1. Click Setup > User.
2. Configure the parameters as appropriate.
3. Click Apply to send and save the new settings to the meter.
Device log export setup
You can set up the meter to export its logs to a web server.
NOTE: Device log export times can vary exponentially, depending on the number of
records to export. To avoid long log export times, consider reducing the logging
frequency for the recorded items or selecting a more frequent log export schedule
(e.g., weekly instead of monthly).
1. Click Setup > Device Log Export.
2. Make sure that the Transport setting is enabled (e.g., set to HTTP). Configure the
parameters as appropriate.
User Accounts
Parameter
Description
Name
Lists the current usernames for accessing the meter. You can add a new user by
typing the username in a blank cell.
To remove an existing user, select the name and press Delete on your keyboard.
Password
1
1
Always record changes or additions to the username and password list and store the list in a safe place.
Lists the current password associated with each user. After adding a new username,
you can type a password to associate it with the username. As you enter characters
for your password, the status bar changes to indicate the password strength (weak,
medium, strong or very strong).
Group Select the group the username belongs to (e.g., web user or product master).
Language Select the language the webpages are displayed in for the selected username.
Device Log Export
Parameter Values Description
Transport Disabled, HTTP
Select Disabled to disable exporting of meter data logs,
or select HTTP to enable exporting of meter data logs.
Schedule Daily, Weekly, Monthly
Select Daily to set the meter data log export to once a
day. Use the Time of Day field to select what time the
data log export occurs each day.
Select Weekly to set the meter data log export to once a
week. Use the Time of Day and Day of Week fields to
select what time and day the data log export occurs each
week.
Select Monthly to set the meter data log export to once a
month. Use the Time of Day and Day of Month fields to
select what time and day the data log export occurs each
month.
HTTP Parameters
Server IP Address Enter the IP address of the server for the data log export.
Server TCP Port Enter the server port number for HTTP communications.
Proxy Server IP Address Enter the proxy server IP address.
Proxy Server TCP Port Enter the proxy server TCP port number.
PATH
Enter the network path of the folder where the data logs
are to be exported.
Field Name Enter the name of the exported data log.
Host Name If using a virtual host name, enter the name here.
Username Enter the username for accessing the server.
Password Enter the password for accessing the server.