Schneider Electric HRB1684301-01 Marine Instruments User Manual


 
HRB1684301-01 59
Chapter 6 Meter logging
This section describes the meter’s logging feature. Meter data and events are stored in
these logs:
Data log
Alarm log
Maintenance log
Data log
The meter is shipped from the factory with data logging enabled for selected values.
Typically, delivered energy (kWh, kVARh and kVAh) is logged by default, but you can
configure the meter to record other measurements.
Setting up the data log
Use ION Setup to configure data logging. You can select up to 14 items to record in the
data log and the frequency (logging interval) that you want those values updated.
1. Start ION Setup and open your meter in setup screens mode (View > Setup
Screens). See the ION Setup Help for instructions.
2. Double-click Data Log #1.
3. Set up the logging frequency and measurements/data to log.
4. Click OK, then Send to save the changes to the meter.
Saving the data log contents
You can use ION Setup or the meter webpages to save the contents of the data log.
NOTICE
LOST DATA
Save the contents of the data log before configuring it.
Failure to follow these instructions can result in data loss.
Data Log #1 setup parameters
Parameter Values Description
Status Enable, Disable
Set this parameter to enable or disable data
logging in the meter.
Interval
1 minute, 5 minutes,
10 minutes, 15 minutes,
30 minutes, 1 hour,
24 hours
Select a time value to set the logging frequency.
Channels
Items available for
logging can vary based
on the meter type.
Select an item to record from the “Available”
column, then click the double-right arrow button to
move the item to the “Selected” column.
To remove an item, select it from the “Selected”
column then click the double-left arrow button.