Schneider Electric HRB1684301-01 Marine Instruments User Manual


 
32 HRB1684301-01
Chapter 3—Front panel display and meter setup PowerLogic™ PM5500 series user manual
Related topics
See “Troubleshooting LED indicators” on page 125 for additional maintenance
information.
Alarm / energy pulsing LED modes
The (orange) alarm / energy pulsing LED can be configured for alarm notification or
energy pulsing.
When configured for alarm notification, this LED flashes when a high, medium or
low priority alarm is tripped. The LED provides a visual indication of an active alarm
condition, or an inactive but unacknowledged high priority alarm.
When configured for energy pulsing, this LED flashes at a rate proportional to the
amount of energy consumed. This is typically used to verify the power meter’s
accuracy.
Related topics
See “Energy pulsing” on page 81 for details on changing the LED mode for energy
pulsing applications.
See “LED alarm indicator” on page 101 for details on changing the LED mode for
alarming applications.
Notification icons
To alert you about meter state or events, notification icons appear at the top left or top
right corner of the display screen.
Notification icons
Icon Description
The wrench icon indicates that the power meter is in an overvoltage condition or requires
maintenance. It could also indicate that the energy LED is in an overrun state. See
“Maintenance and upgrades” on page 121.
The alarm icon indicates an alarm condition has occurred. See “Alarm display and
notification” on page 102 and “Alarm priorities” on page 96.