Schneider Electric HRB1684301-01 Marine Instruments User Manual


 
64 HRB1684301-01
Chapter 7—Viewing meter data PowerLogic™ PM5500 series user manual
Related topics
See “Multi-tariff feature” on page 105.
Power Factor
Frequency
Total harmonic distortion
Related topics
See “Power quality” on page 121.
Unbalance
PF
True
Disp
PF
True
True power factor values per phase and total (PFa [PF1], PFb
[PF2], PFc [PF3], Total), PF sign, and load type (capacitive =
lead, inductive = lag).
Disp
Displacement power factor values per phase and total (PFa
[PF1], PFb [PF2], PFc [PF3],, Total), PF sign, and load type
(capacitive = lead, inductive = lag).
Hz
(F)
Hz [F]
Frequency (Freq), average voltage (Vavg), average current (Iavg) and total power factor (PF) values.
THD
THD
thd
Amps (I)
V L-L (U)
V L-N (V)
Amps (I)
V L-L (U)
V L-N (V)
THD
THD THD (ratio of harmonic content to the fundamental) for phase
currents (Ia [I1], Ib [I2], Ic [I3], In), line-to-line voltages(Vab [U12],
Vbc [U23], Vca [U31]) and line-to-neutral voltages (Van [V1],
Vbn [V2], Vcn [V3]).
Amps [I], V L-L [U], V L-N [V]
thd thd (ratio of harmonic content to the rms value of total harmonic
content) phase currents (Ia [I1], Ib [I2], Ic [I3], In), line-to-line
voltages(Vab [U12], Vbc [U23], Vca [U31]) and line-to-neutral
voltages (Van [V1], Vbn [V2], Vcn [V3]).
Amps [I], V L-L [U], V L-N [V]
Unbal
Unbal
Percent unbalance readings for line-to-line voltage (V L-L [U]), line-to-neutral voltage (V L-N [V]) and current
(Amps [I]).