Schneider Electric HRB1684301-01 Marine Instruments User Manual


 
PowerLogic™ PM5500 series user manual Chapter 3—Front panel display and meter setup
HRB1684301-01 37
7. Press Yes to save your changes.
Related topics
See “Power system” on page 20 for descriptions and symbols of the different
electrical power systems supported by the meter.
See “Meter configuration using ION Setup” on page 53 to set up the meter using
ION Setup.
Configuring advanced setup parameters
The advanced setup screens let you configure the following:
Load timer setpoint: defines the active load current, which is the minimum input
current required to start and keep the active load timer counting.
Peak current demand for total demand distortion: specifies the minimum current
demand value required to include in total demand distortion calculations.
1. Navigate to Maint > Setup.
2. Enter the setup password (default is “0”), then press OK.
3. Navigate to Meter > Advan.
4. Move the cursor to point to the parameter you want to modify, then press Edit.
5. Modify the parameter as required, then press OK.
6. Move the cursor to point to the next parameter you want to modify, press Edit,
make your changes, then press OK.
7. Press Yes to save your changes.
Sys Frequency (Hz) 50, 60
Select the frequency of the electrical power
system, in Hz.
Phase Rotation ABC, CBA Select the phase rotation of the 3-phase system.
Basic setup parameters (Continued)
Parameter Values Description
Advanced setup menu tree
Advanced setup parameters
Parameter Values Description
Label
This label identifies the device, e.g., “Power
Meter”. You cannot use the front panel to edit
this parameter. Use ION Setup to change the
device label.
Load Timer Setpt (A) 0 - 9
Specifies the minimum average current at the
load before the timer starts. The meter begins
counting the number of seconds the load timer
is on (i.e., whenever the readings are equal to
or above this average current threshold.
Pk I dmd for TDD (A) 0 - 9
Specifies the minimum peak current demand
at the load for inclusion in total demand
distortion (TDD) calculations. If the load
current is below the minimum peak current
demand threshold, the meter does not use the
readings to calculate TDD. Set this to “0”
(zero) if you want the power meter to use the
metered peak current demand for this
calculation.