Emerson Process Management 3144P Marine Instruments User Manual


 
Reference Manual
00809-0100-4021, Rev DA
November 2004
Rosemount 3144P
4-28
FOUNDATION Fieldbus
FOUNDATION Fieldbus If a malfunction is suspected despite the absence of a diagnostics message,
follow the procedures described in Table 4-13 to verify that transmitter
hardware and process connections are in good working order. Under each of
symptoms, specific suggestions are offered for solving problems. Always deal
with the most likely and easiest-to-check conditions first.
Table 4-13. F
OUNDATION fieldbus Troubleshooting
Symptom Potential Source Corrective Action
Transmitter does not
Communicate with the
Configuration Interface
Loop Wiring
Check for adequate voltage to the transmitter. The transmitter requires
between 9.0 and 32.0 V at the terminals to operate and provide complete
functionality
Check for intermittent wire shorts, open circuits, and multiple grounds.
Network parameters
See page Table 7-2 on page 7-3
High Output
Sensor Input Failure
or Connection
Enter the transmitter test mode to isolate a sensor failure.
Check for a sensor open circuit.
Check the process variable to see if it is out of range.
Loop Wiring
Check for dirty or defective terminals, interconnecting pins, or receptacles.
Electronics Module
Enter the transmitter test mode to isolate a module failure.
Check the sensor limits to ensure calibration adjustments are within the
sensor range.
Erratic Output
Loop Wiring
Check for adequate voltage to the transmitter. The transmitter requires
between 9.0 and 32.0 V at the terminals to operate and provide complete
functionality
Check for intermittent wire shorts, open circuits, and multiple grounds.
Electronics Module
Enter the transmitter test mode to isolate module failure.
Low Output or No Output
Sensor Element
Enter the transmitter test mode to isolate a sensor failure.
Check the process variable to see if it is out of range.
Loop Wiring
Check for adequate voltage to the transmitter. The transmitter requires
between 9.0 and 32.0 V at the terminals to operate and provide complete
functionality
Check for wire shorts and multiple grounds.
Check the loop impedance.
Check wire insulation to detect possible shorts to ground.
Electronics Module
Check the sensor limits to ensure calibration adjustments are within the
sensor range.
Enter the transmitter test mode to isolate an electronics module failure.