Emerson Process Management 3144P Marine Instruments User Manual


 
Reference Manual
00809-0100-4021, Rev DA
November 2004
Rosemount 3144P
2-8
In Conjunction with a
Rosemount 333 HART
Tri-Loop (HART / 4–20
mA only)
Use the dual-sensor option 3144P transmitter that is operating with two
sensors in conjunction with a 333 HART Tri-Loop
®
HART-to-Analog Signal
Converter to acquire an independent 4–20 mA analog output signal for each
sensor input. The 3144P transmitter can be configured to output four of the six
following digital process variables:
•Sensor 1
•Sensor 2
Differential temperature
Average temperature
First good temperature,
Transmitter terminal temperature.
The HART Tri-Loop reads the digital signal and outputs any or all of these
variables into as many as three separate 4–20 mA analog channels.
Refer to Figure 2-6 for basic installation information. Refer to the 333 HART
Tri-Loop HART-to-Analog Signal Converter Reference Manual (document
number 00809-0100-4754) for complete installation information.
Figure 2-6. HART Tri-Loop
Installation Flowchart
(1)
(1) See “Use with the HART Tri-Loop” on page 3-24 for configuration information.
START
HERE
Unpack the
Tri-Loop
Review the
Tri-Loop
Reference
Manual
Install the
3144P
Set the 3144P
Burst
Command
Order
Set the 3144P
to Burst HART
Command 3
Review
Tri-Loop
Installation
Considerations
Mount the
Tri-Loop to a
DIN Rail
Run Wires from
3144P to Burst
Input Terminals
Install Channel
1 Wires from
Tri-Loop to
Control Room
INSTALL THE
TRI-LOOP
OPTIONAL:
Install Channel
2 Wires from
Tri-Loop to
Control Room
OPTIONAL:
Install Channel
3 Wires from
Tri-Loop to
Control Room
Pass System
Test?
COMMISSION
THE TRI-LOOP
Configure the
Tri-Loop to
Receive 3144P
Burst
Commands
3144P
Installed?
Refer to the
HART Tri-Loop
Reference
Manual
DONE
No
Yes
Yes
No