Emerson Process Management 3144P Marine Instruments User Manual


 
Reference Manual
00809-0100-4021, Rev DA
November 2004
4-9
Rosemount 3144P
FOUNDATION Fieldbus
ADVISE_ACTIVE
The ADVISE_ACTIVE parameter displays which of the advisories is
active. Only the advisory with the highest priority will be displayed. This
priority is not the same as the ADVISE_PRI parameter described above.
This priority is hard coded within the device and is not user configurable.
ADVISE_ALM
ADVISE_ALM is an alarm indicating advisory alarms. These conditions do
not have a direct impact on the process or device integrity.
Recommended Actions
for PlantWeb Alerts
RECOMMENDED_ACTION
The RECOMMENDED_ACTION parameter displays a text string that will give
a recommended course of action to take based on which type and which
specific event of the PlantWeb alerts are active.
Table 4-2.
RB.RECOMMENDED_ACTION
Resource Block
Diagnostics
Table 4-3. Resource Block
BLOCK_ERR messages
Block Errors
Table 4-3 lists conditions reported in the BLOCK_ERR parameter.
Alarm Type
Failed/Maint/Advise
Active Event
Recommended Action
Text String
PlantWeb Alerts
None None No action required
Advisory
NV Writes Deferred Non-volatile writes have been deferred, leave
the device powered until the advisory goes
away
Maintenance
Configuration Error Re-write the Sensor Configuration
Primary Value
Degraded
Confirm the operating range of the applied
sensor and/or verify the sensor connection and
device environment
Calibration Error Retrim the device
Secondary Value
Degraded
Verify the ambient temperature is within
operating limits
Failed
Electronics Failure Replace the Device
HW / SW Incompatible Verify the Hardware Revision is compatible
with the Software Revision
NV Memory Failure Reset the device then download the Device
Configuration
Primary Value Failure Verify the instrument process is within the
Sensor range and / or confirm sensor
configuration and wiring.
Secondary Value
Failure
Verify the ambient temperature is within
operating limits
Diagnostic
Error
Sensor Drift Alarm or
Hot BU active
Verify sensor range and/or confirm sensor
configuration and wiring.
Condition Name and Description
Other
Device Needs Maintenance Now
Memory Failure: A memory failure has occurred in FLASH, RAM, or EEPROM memory
Lost NV Data: Non-volatile data that is stored in non-volatile memory has been lost.
Device Needs Maintenance Now
Out of Service: The actual mode is out of service.