Emerson Process Management 3144P Marine Instruments User Manual


 
Reference Manual
00809-0100-4021, Rev DA
November 2004
Rosemount 3144P
4-4
FOUNDATION Fieldbus
Block instantiation is done by the host control system or configuration tool, but
not all hosts are required to implement this functionality. Please refer to your
specific host or configuration tool manual for more information.
Capabilities Virtual Communication Relationship (VCRs)
There are a total of 20 VCRs. One is permanent and 19 are fully configurable
by the host system. Thirty link objects are available.
Table 4-1. Network Parameters
Block Execution times
FOUNDATION FIELDBUS
FUNCTION BLOCKS
For reference information on the Resource, Sensor Transducer, AI, LCD
Transducer blocks refer to “Foundation Fieldbus Block Information” on
page A-1. Reference information on the PID block can be found in the
Function Block manual document number 00809-0100-4783.
Resource Block (index number 1000)
The Resource Function Block (RB) contains diagnostic, hardware and
electronics information. There are no linkable inputs or outputs to the
Resource Block.
Sensor Transducer Block (index number 1100)
The Sensor Transducer Function Block (STB) temperature measurement
data, including sensor and terminal temperature, The STB also includes
information about sensor type, engineering units, linearization, reranging,
damping, temperature compensation, and diagnostics.
LCD Transducer Block (index number 1200)
The LCD Transducer Block is used to configure the LCD display.
Network Parameter Value
Slot Time 8
Maximum Response Delay 2
Maximum Inactivity to Claim LAS Delay 32
Minimum Inter DLPDU Delay 8
Time Sync class 4 (1 ms)
Maximum Scheduling Overhead 21
Per CLPDU PhL Overhead 4
Maximum Inter-channel Signal Skew 0
Required Number of Post-transmission-gab-ext Units 0
Required Number of Preamble-extension Units 1
Block Execution Time
Resource
Transducer
LCD Block
Advanced Diagnostics
Analog Input 1, 2, 3 60 ms
PID 1 and 2 with Autotune 90 ms
Input Selector 65 ms
Signal Characterizer 45 ms
Arithmetic 60 ms
Output Splitter 60 ms