Monitor display and monitor output signal
4
PARAMETERS
4.12.5 How to calibrate the terminal FM when using the operation panel (FR-DU07)
Perform the following procedure to calibrate terminal FM using the operation panel FR-DU07. Refer to page 159 for
the details of parameters.
REMARKS
Calibration can also be made for external operation. Set the frequency in External operation mode, and make calibration in
the above procedure.
Calibration is available even during operation.
For the operating procedure using the parameter unit (FR-PU04/FR-PU07), refer to the parameter unit instruction manual.
Parameters referred to
C0(Pr.900) FM terminal calibration Refer to page 159
C1(Pr.901) AM terminal calibration Refer to page 159
Press to return to the indication (step 8).
13. Press . Setting is complete.
2. Press to choose the parameter
setting mode.
3.
Flicker...Parameter setting complete!!
Flicker...Parameter setting complete!!
Analog indicator
6. Press to set.
7.
Turn until appears.
5.
Turn to change it
to the setting value of
" ".
4. Press to read the present set value.
" " (initial value) appears.
1.Confirmation of the RUN indicator and
operation mode indicator
8. Press to display .
10. Press to enable setting.
11. If the inverter is at a stop, (press
or ) to start the inverter.
(Motor needs not be connected.)
12. Turn to adjust the indicator needle
to the desired position.
( ) )
By turning , you can read another parameter.
+
-
The parameter
number read
previously appears.
(When Pr. 54=1)
Press twice to show the next parameter ( ).
Display
Operation
9.
Turn until appears.
Set to
C0 FM terminal calibration
.
C0 to C7
setting
is enabled.
The monitor set to Pr. 54 FM terminal
function selection is displayed.