Mitsubishi Electronics FR-F720P Marine Battery User Manual


 
65
Parameter List
Parameter list
4
PARAMETERS
Acceleration/
deceleration times
20
Acceleration/deceleration reference
frequency
1 to 400Hz 0.01Hz 60Hz 109
21
Acceleration/deceleration time
increments
0, 1 1 0 109
Stall
prevention
22
Stall prevention operation level 0 to 150%, 9999 0.1% 120% 91
23
Stall prevention operation level
compensation factor at double speed
0 to 200%, 9999 0.1% 9999 91
Multi-speed
setting
24
to
27
Multi-speed setting (4 speed to 7
speed)
0 to 400Hz, 9999 0.01Hz 9999 102
28
Multi-speed input compensation
selection
0, 1 1 0 106
29
Acceleration/deceleration pattern
selection
0, 1, 2, 3, 6 1 0 115
30
Regenerative function selection
0, 2, 10, 20/
0, 1, 2, 10, 11, 20, 21
*2
10125
Frequency jump
31
Frequency jump 1A 0 to 400Hz, 9999 0.01Hz 9999 97
32
Frequency jump 1B 0 to 400Hz, 9999 0.01Hz 9999 97
33
Frequency jump 2A 0 to 400Hz, 9999 0.01Hz 9999 97
34
Frequency jump 2B 0 to 400Hz, 9999 0.01Hz 9999 97
35
Frequency jump 3A 0 to 400Hz, 9999 0.01Hz 9999 97
36
Frequency jump 3B 0 to 400Hz, 9999 0.01Hz 9999 97
37
Speed display 0, 1 to 9998 1 0 150
Frequency
detection
41
Up-to-frequency sensitivity 0 to 100% 0.1% 10% 144
42
Output frequency detection 0 to 400Hz 0.01Hz 6Hz 144
43
Output frequency detection for
reverse rotation
0 to 400Hz, 9999 0.01Hz 9999 144
Second functions
44
Second acceleration/deceleration
time
0 to 3600/360s 0.1/0.01s 5s 109
45
Second deceleration time 0 to 3600/360s, 9999 0.1/0.01s 9999 109
46
Second torque boost 0 to 30%, 9999 0.1% 9999 87
47
Second V/F (base frequency) 0 to 400Hz, 9999 0.01Hz 9999 98
48
Second stall prevention operation
current
0 to 150% 0.1% 120% 91
49
Second stall prevention operation
frequency
0 to 400Hz, 9999 0.01Hz 0Hz 91
50
Second output frequency detection 0 to 400Hz 0.01Hz 30Hz 144
51
Second electronic thermal O/L relay
0 to 500A, 9999/
0 to 3600A, 9999
*2
0.01/0.1A *2 9999 117
Monitor functions
52
DU/PU main display data selection
0, 5, 6, 8 to 14, 17, 20,
23 to 25, 50 to 57, 100
10152
54
FM terminal function selection
1 to 3, 5, 6, 8 to 14, 17,
21, 24, 50, 52, 53
11152
55
Frequency monitoring reference 0 to 400Hz 0.01Hz 60Hz 157
56
Current monitoring reference 0 to 500A/0 to 3600A *2 0.01/0.1A *2
Rated
inverter
current
157
Function Parameters
Name Setting Range
Minimum
Setting
Increments
Initial
Value
Refer
to
Page
Customer
Setting