4.26 Parameter copy and parameter verification
4.26.1 Parameter copy
PCPY Setting Description
0 Cancel
1 Copy the source parameters to the operation panel.
2 Write the parameters copied to the operation panel into the destination inverter.
3 Verify parameters in the inverter and operation panel. (Refer to page 302.)
Parameter settings can be copied to multiple inverters.
REMARKS
· When the copy destination inverter is not the FR-F700(P) series or parameter copy write is performed after parameter copy read is
stopped, "model error ( )" is displayed.
· Refer to the parameter list on
page 368 and later for availability of parameter copy.
· When the power is turned OFF or an operation panel is disconnected, etc. during parameter copy write, perform write again or check
the values by parameter verification.
· Initial settings of certain parameters are different for different capacities, so some parameter settings may be automatically changed
when parameter copy is performed from a different-capacity inverter. After performing a parameter copy from a different-capacity
inverter, check the parameter settings. Especially under IPM motor control, check the Pr.80 Motor capacity setting before starting the
operation. (Refer to the parameter list (page 64) for the parameters with different initial settings for different capacities.)
1.Connect the operation panel to the
copy source inverter.
Connect it during a stop.
Display
Operation
2.Press to choose the parameter
setting mode.
Flicker ··· Parameter copy complete!!
6.Press to copy the source parameters
to the operation panel.
4.Press to to read the present set value.
" "(initial value) appears.
Flicker ··· Parameter copy complete!!
9.Press to write the parameters copied to
the operation panel to the destination inverter.
3.Turn until (parameter copy)
appears.
5.Turn to change it to
the setting value " ".
The frequency flickers
for about 30s
The frequency flickers
for about 30s
About 30s later
10.When copy is completed,
" " and " " flicker.
11.After writing the parameter values to the copy
destination inverter, always reset the inverter,
e.g. switch power OFF once, before starting operation.
7.Connect the operation panel to the
copy source inverter.
8.After performing steps 2 to 5,
turn to change it to " ".
The parameter
number read
previously appears.