Mitsubishi Electronics FR-F720P Marine Battery User Manual


 
258
Communication operation and setting
Parameter
Faults history
Fault code list
Parameters
Register Parameter Name Read/Write Remarks
0 to 999
41000 to
41999
Refer to the parameter list (page
64) for the parameter names.
Read/write
The parameter number + 41000 is the
register number.
C2(902) 41902
Terminal 2 frequency setting
bias (frequency)
Read/write
C3(902)
42092
Terminal 2 frequency setting
bias (analog value)
Read/write
The analog value (%) set to C3 (902) is
read.
43902
Terminal 2 frequency setting
bias (terminal analog value)
Read
The analog value (%) of the voltage (current)
applied to the terminal 2 is read.
125(903) 41903
Terminal 2 frequency setting
gain (frequency)
Read/write
C4(903)
42093
Terminal 2 frequency setting
gain (analog value)
Read/write
The analog value (%) set to C4 (903) is
read.
43903
Terminal 2 frequency setting
gain (terminal analog value)
Read
The analog value (%) of the voltage
(current) applied to the terminal 2 is read.
C5(904) 41904
Terminal 4 frequency setting
bias (frequency)
Read/write
C6(904)
42094
Terminal 4 frequency setting
bias (analog value)
Read/write
The analog value (%) set to C6 (904) is
read.
43904
Terminal 4 frequency setting
bias (terminal analog value)
Read
The analog value (%) of the current (voltage)
applied to the terminal 4 is read.
126(905) 41905
Terminal 4 frequency setting
gain (frequency)
Read/write
C7(905)
42095
Terminal 4 frequency setting
gain (analog value)
Read/write
The analog value (%) set to C7 (905) is
read.
43905
Terminal 4 frequency setting
gain (terminal analog value)
Read
The analog value (%) of the current (voltage)
applied to the terminal 4 is read.
C42(934) 41934
PID display bias coefficient Read/write
C43(934)
42124
PID display bias analog value
Read/write
The analog value (%) set to C43 (934) is
read.
43934
PID display bias analog value
(terminal analog value)
Read
The analog value (%) of the current (voltage)
applied to the terminal 4 is read.
C44(935) 41935
PID display gain coefficient
Read/write
C45(935)
42125
PID display gain analog value
Read/write
The analog value (%) set to C45 (935) is
read.
43935
PID display gain analog value
(terminal analog value)
Read
The analog value (%) of the current
(voltage) applied to the terminal 4 is read.
Register Definition Read/Write Remarks
40501 Fault history 1 Read/write
Being 2 bytes in length, the data is stored as
"H00". Refer to the lowest 1 byte for the fault
code.
Performing write using the register 40501 batch-
clears the faults history. Set any value as data.
40502 Fault history 2 Read
40503 Fault history 3 Read
40504 Fault history 4 Read
40505 Fault history 5 Read
40506 Fault history 6 Read
40507 Fault history 7 Read
40508 Fault history 8 Read
Data Description
H00 No fault
H10 OC1
H11 OC2
H12 OC3
H20 OV1
H21 OV2
H22 OV3
H30 THT
H31 THM
H40 FIN
H50 IPF
H51 UVT
H52 ILF
H60 OLT
H61 SOT
H70 BE
H80 GF
H81 LF
H90 OHT
Data Description
H91 PTC
HA0 OPT
HA1 OP1
HB0 PE
HB1 PUE
HB2 RET
HB3 PE2
HC0 CPU
HC1 CTE
HC2 P24
Data Description
HC4 CDO
HC5 IOH
HC6 SER
HC7 AIE
HE6 PID
HF1 E.1
HF5 E.5
HF6 E.6
HF7 E.7
HFD E.13
Data Description