Mitsubishi Electronics FR-F720P Marine Battery User Manual


 
64
Parameter list
4.2 Parameter list
4.2.1 Parameter list
In the initial setting, only the simple mode parameters are displayed.
Set Pr. 160 User group read selection as required.
To use the inverter under IPM motor control, refer to page 77.
Parameter Name
Initial
Value
Setting
Range
Remarks
160
User group read
selection
9999
9999 Only the simple mode parameters can be displayed.
0
Simple mode and extended mode parameters can be
displayed.
1
Only the parameters registered in the user group can be
displayed.
REMARKS
The parameters marked are the simple mode parameters.
The parameters marked with in the table allow their settings to be changed during operation even if "0" (initial
value) is set in Pr. 77 Parameter write selection.
Refer to the appendix 2 (page 368) for instruction codes for communication and availability of parameter clear, all clear, and
parameter copy of each parameter.
.........Specifications differ according to the date assembled. Refer to page 378 to check the SERIAL number.
Function Parameters
Name Setting Range
Minimum
Setting
Increments
Initial
Value
Refer
to
Page
Customer
Setting
Basic functions
0
Torque boost 0 to 30% 0.1%
6/4/3/2/
1.5/1%
*1
87
1
Maximum frequency 0 to 120Hz 0.01Hz
120/60Hz
*2
96
2
Minimum frequency 0 to 120Hz 0.01Hz 0Hz 96
3
Base frequency 0 to 400Hz 0.01Hz 60Hz 98
4
Multi-speed setting (high speed) 0 to 400Hz 0.01Hz 60Hz 102
5
Multi-speed setting (middle speed) 0 to 400Hz 0.01Hz 30Hz 102
6
Multi-speed setting (low speed) 0 to 400Hz 0.01Hz 10Hz 102
7
Acceleration time 0 to 3600/ 360s 0.1/0.01s 5s/15s *3 109
8
Deceleration time 0 to 3600/ 360s 0.1/0.01s 10s/30s *3 109
9
Electronic thermal O/L relay 0 to 500/0 to 3600A 0.01/0.1A
Rated
inverter
current
117
DC injection
brake
10
DC injection brake operation
frequency
0 to 120Hz, 9999 0.01Hz 3Hz 123
11
DC injection brake operation time 0 to 10s 0.1s 0.5s 123
12
DC injection brake operation voltage 0 to 30% 0.1% 4/2/1% *4 123
13
Starting frequency 0 to 60Hz 0.01Hz 0.5Hz 113
14
Load pattern selection 0, 1 1 1 100
Jog
operation
15
Jog frequency 0 to 400Hz 0.01Hz 5Hz 104
16
Jog acceleration/deceleration time 0 to 3600/360s 0.1/0.01s 0.5s 104
17
MRS input selection 0, 2, 4 1 0 136
18
High speed maximum frequency 120 to 400Hz 0.01Hz
120/60Hz
*2
96
19
Base frequency voltage 0 to 1000V, 8888, 9999 0.1V 9999 98